OCH790 _137
Self check
M-NET address
Delete error history?
Cancel
OK
Self check
M-NET address
Error history deleted
Return:
13-7-2. PAR-SL97A-E
When a malfunction occurs to air conditioners, both of the indoor unit and the outdoor unit will stop and the operation
lamp will blink to inform the unusual stop.
Operating instructions
1.
Press the
CHECK
button twice.
CHECK
appears, and the refrigerant address ˝00˝ blinks.
Make sure that the remote controller’s display has stopped before continuing.
2. Press the
buttons to select the refrigerant address of the indoor unit for self-diagnosis.
Set refrigerant address using the outdoor unit’s DIP switch (SW1).
For more information, see the outdoor unit installation manual.
3. Point the remote controller at the sensor of the indoor unit and press the
h
button.
If an air conditioner error occurs, the indoor unit’s sensor emits an intermittent buzzer sound, the operation light
blinks, and the check code is output. (It takes 3 seconds at most for check code to appear.)
4.
Point the remote controller at the sensor of the indoor unit and press the
button.
The check mode is cancelled.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK
display
Temperature
button
CHECK
button
Refrigerant
address
display
HOUR
button
ON/OFF
button
13-7-3. PAR-SL101A-E
Operating instructions
1.
Press the
button to stop the air conditioner.
If the weekly timer is enabled (
is shown on the display), press the
button to disable it (
is off).
2. Press the
button for 5 seconds.
CHECK
appears and the unit starts the self-check mode.
3. Press the
button to select the refrigerant address (M-NET address) of the indoor unit for which you want to per-
form the self-check.
4.
Press the
button.
If an error is detected, the check code is indicated by the number of beeps from the indoor unit and the number of
blinks of the OPERATION INDICATOR lamp.
5.
Press the
button.
CHECK
and the refrigerant address (M-NET address) go off and the selfcheck is completed.