OCH790 _100
8-10. Outdoor unit information display
SW: setting
0: OFF
1: ON
SW1
setting
Contents
LED1, 2
No.
12345678
1
2
3
4
5
6
7
8
0
00000000
Relay output (at
normal state)
Compressor
operation
52C
21S4
SV1
(SV2)
—
—
Always
lighting
Error code (at
abnormal state)
0000–9999 (Alternating display of addresses and error code)
Note: When abnormality occurs, check display.
1
10000000 Indoor unit check
status
No.1 unit
check
No.2 unit
check
No.3 unit
check
No.4 unit
check
No.5 unit
check
No.6 unit
check
No.7 unit
check
No.8 unit
check
Note: Light on at time of abnormality
2
01000000
Protection input
High pressure
abnormality
Superheat
due to low
discharge
temperature
Compressor
shell tem
-
perature
abnormality
TH4 abnor-
mality
TH3 abnor-
mality
Outdoor fan
rotation
frequency
abnormality
TH7 abnor-
mality
TH8 abnor-
mality
Note: Display detected microprocessor protection or abnormality
3
11000000
Protection input
Heat sink
overheating
Compressor
over current
interception
Voltage
abnormality
Insufficient
refrigerant
amount
abnormality
Current
sensor/
primary
current abnor-
mality
63LS
abnormality
63HS
abnormality
start over
current
interception
abnormality
delay
Note: Display detected microprocessor protection or abnormality
4
00100000
Protection input
Abnormality
in the number
of indoor units
Address
double setting
abnormality
Indoor unit
capacity error
Over capacity
Indoor unit
address error
Outdoor unit
address error
Current
sensor open/
short
Serial
communica
-
tion abnor-
mality
(outdoor unit)
Note: Display detected microprocessor protection or abnormality
5
10100000 Abnormality delay
display 1
High pressure
abnormality
delay
Superheat
due to low
discharge
temperature
delay
Compressor
shell tem
-
perature
abnormality
delay
TH4 abnor-
mality delay
TH3 abnor-
mality delay
Outdoor fan
rotation
frequency
abnormality
delay
TH7 abnor-
mality delay
TH8 abnor-
mality delay
Note: Display all abnormalities remaining in abnormality delay
6
01100000 Abnormality delay
display 2
Heat sink
overheating
delay
Compressor
over current
interception
delay
Voltage
abnormality
delay
Insufficient
refrigerant
amount
abnormality
delay
Current
sensor/
primary
current abnor-
mality delay
63LS
abnormality
delay
63HS
abnormality
delay
start over
current
interception
abnormality
delay
Note: Display all abnormalities remaining in abnormality delay
7
11100000 Abnormality delay
display 3
63LS
abnormality
delay
TH2 abnor-
mality delay
4-way valve
abnormality
delay
Delay caused
by closed
valve in
cooling mode
Power
module
abnormality
delay
TH6 abnor-
mality delay
Current
sensor open/
short delay
—
Note: Display all abnormalities remaining in abnormality delay
8
00010000 Abnormality delay
history 1
High pressure
abnormality
delay
Superheat
due to low
discharge
temperature
delay
Compressor
shell tem
-
perature
abnormality
delay
TH4 abnor-
mality delay
TH3 abnor-
mality delay
Outdoor fan
rotation
frequency
abnormality
delay
TH7 abnor-
mality delay
TH8 abnor-
mality delay
Note: Display all abnormalities remaining in abnormality delay
9
10010000 Abnormality delay
history 2
Heat sink
overheating
delay
Compressor
over current
interception
delay
Voltage
abnormality
delay
Insufficient
refrigerant
amount
abnormality
delay
Current
sensor/
primary
current abnor-
mality delay
63LS
abnormality
delay
63HS
abnormality
delay
start over
current
interception
abnormality
delay
Note: Display all abnormalities remaining in abnormality delay
10 01010000 Abnormality delay
history 3
63LS
abnormality
delay
TH2 abnor-
mality delay
4-way valve
abnormality
delay
Delay caused
by closed
valve in
cooling mode
Power
module
abnormality
delay
TH6 abnor-
mality delay
Current
sensor open/
short delay
—
Note: Display all abnormalities remaining in abnormality delay
11 11010000 Abnormality code
history 1 (the
latest)
Alternating display of addresses 0000–9999 and abnormality code (including abnormality delay code)
Followings are the delay code and the details of the abnormal delay
1202: Discharge/Comp. temperature, Thermistor <Compressor>(TH4)
1205: Thermistor <Outdoor liquid pipe> (TH3)
1211: Thermistor <Suction pipe> (TH6)
1214: Thermistor <Heat sink> (TH8)
1221: Thermistor <Ambient> (TH7)
1222: Thermistor <HIC> (TH2)
1400: Low pressure sensor
1402: High pressure (63H), High pressure sensor (63HS)
1600: Discharge superheat (SHd), Over charge refrigerant
1601: Insufficient refrigerant, Closed cooling valve
1608: 4-way valve disconnection
4310: Current sensor open/short
4320: Undervoltage, overvoltage, or power module
4330: Heat sink temperature
4350: Power module
4500: Outdoor fan motor
Notes:
• Display abnormalities up to present (including abnormality terminals)
• History record in 1 is the latest; records become older in sequence; history record in 10 is the oldest.
12 00110000 Abnormality code
history 2
13 10110000 Abnormality code
history 3
14 01110000 Abnormality code
history 4
15 11110000 Abnormality code
history 5
16 00001000 Abnormality code
history 6
17 10001000 Abnormality code
history 7
18 01001000 Abnormality code
history 8
19 11001000 Abnormality code
history 9
20
00101000 Abnormality code
history 10 (the
oldest)
21 10101000
Cumulative time
0–9999 (unit: 1 hour)
Note: Display of cumulative compressor operating time
22
01101000
Cumulative time
0–9999 (unit: 10 hours)
Note: Display of cumulative compressor operating time
23
11101000
Outdoor unit oper
-
ation display
Compressor
energizing
Compressor
operating
prohibition
Compressor
in operation
Abnormality
detection
—
—
—
—