OCH790 _39
1302 (UE): High pressure trouble
Chart 4 of 4
Diagnosis of failure
Continued from the previous page.
Replace the SV1.
Replace the 63HS.
Replace the outdoor multi controller circuit
board.
Reconnect the connector or connect it tightly.
Check the 63HS voltage.
Is the resistance detected?
Is the connector for outdoor multi
controller circuit board 63H discon-
nected or loose?
Is the voltage(*) detected?
No
No
No
Yes
Yes
Yes
*For the voltage, refer to "How to check the components".