Minuteman Continuous Power Series UPS
Table 4-2. Alarm Connections
Alarm
Pin Number Connected To
System State
Line Failure
1 - 2
Line OK
1 - 3
Line Failure
Impending Low Battery
4 - 5
Battery Normal
4 - 6
Battery Low
Summary Alarm
7 - 9
UPS ON/OK
7 - 8
UPS Alarm
UPS Bypassed
10 - 11
Inverter Supply
10 - 12
Bypass Supply
Line
Failure
Impending
Low
Battery
Summary
Alarm
UPS
Bypassed
D—connector 15-pin
15 14 13 11 10 12 9 7 8 6 4 5 3 1 2
Figure 4-5. Pin Locations for Each Alarm
REAR PANEL CIRCUIT BREAKERS
The Minuteman Continuous Power Series has two types of output circuit
breakers on the rear panel. The push-button type circuit breaker protects each
standard 5-15R duplex. When the push-button circuit breaker trips, it pops
outs and a green ring appears. Push it in to reset.
C A U T I O N
Pushing in the push-button circuit breaker when it is not
tripped, causes the circuit to open and your load to drop.