Minuteman Continuous Power Series UPS
9.
Connect the AC input and output wiring according to the UPS
Input and Output Wiring Tables and Figures.
Table 3-2 and
Figure 3-6 explain connecting single-phase units. Table 3-3 and
Figure 3-7 explain connecting two-phase units. Check the UPS identifi-
cation label to verify that the power rating for your load matches the
power rating of the UPS. Refer to the terminal block illustrations in
Figure 3-9 and Figure 3-10 for the correct terminal locations. The block
diagram in Figure 3-8 gives an overview of UPS connections.
N O
N O
N O
N O
N O T E
T E
T E
T E
T E
Input Line 2 (IL2) and Output Line 2 (OL2) on the terminal
blocks are used for two-phase units only. These terminals are
not connected on single-phase units.
N O
N O
N O
N O
N O T E
T E
T E
T E
T E
If your UPS has an optional load circuit breaker plate, go to
Installing Output Circuit Breaker later in this section to con-
nect loads through the output circuit breaker.
C A
C A
C A
C A
C A U T I O N
U T I O N
U T I O N
U T I O N
U T I O N
Utility neutral must be connected to the neutral terminal (IL3)
on all hardwired units. Failure to connect the neutral can
damage the unit.
Table 3-2. UPS Input and Output Wiring Chart for Single-Phase Models
AC Input to UPS Input (single-phase)
Connect this Wire
To this Terminal in the UPS
Utility GROUND
Grounding Stud
Utility Neutral
IL3 (Neutral)
Utility Line 1 (hot)
IL1 (Line 1)
Load to UPS Output (single-phase)
Connect this Wire
To this Terminal in the UPS
Load Ground
Grounding Stud
Load Neutral
OL3 (Neutral)
Load Line 1 (hot)
OL1 (Line 1)
SPECIAL CAUTION: THE CP3200 & CP6000, 2 PHASE UNITS, REQUIRE A 4 WIRE INPUT. THIS
UNIT WILL BE DAMAGED, AND WILL NO LONGER FUNCTION IF THE INPUT IS INCORRECTLY
WIRED. DO NOT ATTEMPT TO OPERATE UNIT UNLESS INSTALLED CORRECTLY.
CONSULT WITH A QUALIFIED ELECTRICIAN IF THIS UNIT IS A PLUG AND PLAY (PP) UNIT AND
WALL OUTLET DOES NOT MATCH FOR A DIRECT CONNECTION.
THE FOLLOWING MODELS ARE 2 PHASE UNITS:
1.CP3200
2.CPR3200
3.CP3200-PP
4.CPR3200-PP
5.CP6000
6.CP6000-PP
NOTE
NOTE
CAUTION
!