Minuteman Continuous Power Series UPS
N O T E
LEDs 15-19 are used to select specific output voltages for the
UPS. The default voltage for single-phase units is 120 V nomi-
nal. The default for two-phase units is 208 V or 240 V nominal.
Enable only one voltage selection. If two conflicting voltages
are enabled the voltages will automatically return to the
default.
Table 4-1. LED Parameters
LED
LED
State
Parameter
1
Blinking*
Enable auto frequency detection
Solid
Disabled
2
Blinking
Enable forced 60 Hz frequency regardless of input
Solid*
Disabled
3
Blinking
Enable forced 50 Hz frequency regardless of input
Solid*
Disabled
4
Blinking*
Synch. frequency range A ± 3 Hz
Solid
Disabled
5
Blinking
Synch. frequency range B ± 1 Hz
Solid*
Disabled
6
Blinking
Synch. frequency range C ± 1/2 Hz
Solid*
Disabled
7
Blinking
5minute impending low battery
Solid*
2minute impending low battery
8
Blinking
Disable auto restart
Solid*
Enable auto restart
9
Blinking
Disable site wiring fault
Solid*
Enabled site wiring fault (only 1 phase unit)
10
Blinking
Disable audio alarm
Solid*
Enabled audio alarm
11
Blinking
Enable 2nd RS-232 port for modem (optional)
Solid*
Disabled
12
Blinking*
Disable auto self test
Solid
Enable auto self test (select either 30 or 90 day test from LED 13
or 14. If none is selected, parameter returns to default)
13
Blinking
Enable every-30-day auto self test
Solid*
Disable every-30-day auto self test
14
Blinking
Enable every-90-day auto self test
Solid*
Disable every-90-day auto self test
15
Blinking
Enable 100 V output (200 V output)** nominal
Solid*
Disabled
16
Blinking
Enable 110 V output (220 V output)** nominal
Solid*
Disabled
17
Blinking
Enable 115 V output (230 V output)** nominal
Solid*
Disabled
18
Blinking*
Enable 120 V output (208/240 V output)** nominal
Solid
Disabled
19
Blinking
Enable 127 V output (220/254 V output)** nominal
Solid*
Disabled
* Parameter default. ** Voltage in parenthesis ( ) are applicable for two-phase units.
NOTE
CAUTION!
During configuration mode, "DO NOT" configure the LED #20 to blink. This is for
factory use only, and may damage the UPS. Failure to comply with this directive may
void your warranty!