Installation
As a general rule, Minarik recommends shielding all conductors.
If it is not practical to shield power conductors, Minarik
recommends shielding all logic-level leads. If shielding is not
practical, the user should twist all logic leads with themselves to
minimize induced noise.
It may be necessary to earth ground the shielded cable. If noise is
produced by devices other than the drive, ground the shield at the
drive end. If noise is generated by a device on the drive, ground
the shield at the end away from the drive. Do not ground both
ends of the shield.
If the drive continues to pick up noise after grounding the shield,
it may be necessary to add AC line filtering devices, or to mount
the drive in a less noisy environment.
Logic wires from other input devices, such as motion controllers
and PLL velocity controllers, must be separated from power lines
in the same manner as the logic I/O on this drive.
Under no circumstances should power and logic leads be
bundled together. Induced voltage can cause unpredictable
behavior in any electronic device, including motor controls.
Shielding guidelines
250-0288.qxd 6/9/00 1:05 PM Page 7
Summary of Contents for MMBOSS Series
Page 1: ...Model MMBOSS05 24DC 1Q MMBOSS Series User s Manual...
Page 7: ...Tables Table 1 Line Fuse Chart 8 Table 2 Replacement Parts 41 v...
Page 8: ......
Page 10: ......
Page 11: ...3 Dimensions Figure 1 MMBOSS Series Dimensions...
Page 12: ......
Page 21: ...13 Installation Figure 4 PCB Power Fuse and Motor Connections TO MOTOR DIR COM COM...
Page 28: ......
Page 34: ...Figure 9 Decelerate to Minimum Speed Switch 26 Operation...
Page 52: ...Notes...
Page 53: ...Notes...
Page 54: ...Notes...