TROUBLESHOOTING
message
diagnosis
action
E1 (program)
security code required
enter access code into P000
E2 (run)
totalizer resolution too low
increase value (P631 - P639)
E3 (run)
zero out of range
consider an initial zero P377,
refer to Recalibration\Initial Zero
E4 (run)
span out of range
consider an initial span P388,
refer to Recalibration\Initial Span
E5 (run)
parameter not entered
check parameters P005 - P017
for entry
E6 (run)
zero calibration required
do a zero calibration
E7 (run)
span calibration required
do a span calibration
E8 (program)
parameter value error
check that value is valid
E9(run)
auto zero out of range
auto zero has accumulated
deviation beyond 2% from
last operator initial zero. If
error is not caused by material
on belt, then do an operator
initiated zero.
E10 (run)
rate or span out of range
loading on belt is 300% of
rated load or greater.
Investigate and if no mechanical
cause, check to see if re-rating
the design rate is required.
E11 (run)
speed greater than twice
check design belt speed against
the design speed
actual belt speed,check speed
constant, perform speed constant
adjust (P018) if necessary.
E12 (factoring)
span out of range
test load is either too low or
beyond 100% of design load
(P952). Replace test weight with
a heavier or lighter weight and try
factoring again.
E101 (run)
load cell ’A’
check wiring
E102 (run)
load cell ’B’
check wiring
APPENDICES
PL-531
80
Summary of Contents for Accumass BW100
Page 1: ...Accumass BW100 May 1997 Instruction Manual PL 531 33455310 Rev 1 5...
Page 20: ...INSTALLATION PL 531 20...
Page 34: ...START UP PL 531 34...
Page 48: ...RECALIBRATION PL 531 48...
Page 56: ...OPERATION PL 531 56...
Page 76: ...PARAMETER DESC PL 531 76...