![Milltronics Accumass BW100 Instruction Manual Download Page 66](http://html1.mh-extra.com/html/milltronics/accumass-bw100/accumass-bw100_instruction-manual_1796978066.webp)
P368
direct span
This parameter allows the span reference count to be viewed or entered directly.
Direct entry is intended for use when replacing software or hardware
and it is not convenient to perform an initial span at that time.
P370
zero limit
Sets the zero calibration deviation limit from the last initial zero. If the
accumulated deviation exceeds the limit, the zero calibration is aborted (E3).
entry: 0 =
±
12.5% of initial zero
1 =
±
2% of initial zero
P377
initial zero
The initial zero is the reference zero to which all subsequent operator
initiated zero calibrations are compared in determining whether they
have deviated beyond the zero limit (P370)
entry: 0 = idle
1 = initial zero
Refer to Recalibration\Initial Zero for use of this function.
P388
initial span
The initial span is the reference to which all subsequent span calibrations
are compared in determining whether they have deviated beyond 12.5%
of the initial span.
entry: 0 = idle
1 = initial span
Refer to Recalibration\Initial Span for use of this function.
97\10\29
PARAMETER DESC.
PL-531
66