![Milltronics Accumass BW100 Instruction Manual Download Page 7](http://html1.mh-extra.com/html/milltronics/accumass-bw100/accumass-bw100_instruction-manual_1796978007.webp)
SPECIFICATIONS
Power:
» standard:
» 100/115/200/230 V ac
±
15%, 50/60 Hz, 15 VA
» optional:
» 10 - 15 V dc, 15 W
» 18 - 30 V dc, 15 W
Application:
» compatible with Mass Dynamics belt scales MSI, MSL,
MMW and MIC, or equivalent
Accuracy:
» 0.1% of full scale
Resolution:
» 0.02% of full scale
Environmental: » location:
» indoor / outdoor
» altitude:
» 2000 m max
» ambient temperature: » -20 to 50 °C (-5 to 122 °F)
» relative humidity:
» suitable for outdoor (Type 4X /
NEMA 4X / IP 65 enclosure)
» installation category: » II
» pollution degree:
» 4
Enclosure:
» polypropylene alloy
» Type 4X / NEMA 4X / IP 65
» sealed electronics compartment
» integral junction box with termination block for 0.2 - 4 mm
2
solid
» or 0.2 - 2.5 mm
2
stranded (12 - 24 AWG)
Programming: » via local 4 member keypad with silicone boot and/or Dolphin interface
Display:
» 38 x 100 mm (1.5 x 4") multi-field liquid crystal display
Memory:
» program stored in non-volatile FLASH memory,
upgradable via Dolphin interface
» parameters stored in non-volatile EEPROM
Inputs:
» load cell:
» 0 - 45 mV dc per load cell
» speed sensor:
» pulse train: 0-5 V low, 0-15 V high, 1 to 2000 Hz,
or
» open collector switch,
or
» relay dry contact
» auto zero:
» dry contact from external device
Outputs:
» analog:
» optically isolated 0/4 - 20 mA
» 750
Ω
max loading
» resolution: 0.1% of 20 mA
» load cell:
» 10 V dc compensated for strain gauge type,
2 cells max
» speed sensor:
» 12 V dc, 50 mA max excitation
97/07/07
SPECIFICATIONS
PL-531
7
Summary of Contents for Accumass BW100
Page 1: ...Accumass BW100 May 1997 Instruction Manual PL 531 33455310 Rev 1 5...
Page 20: ...INSTALLATION PL 531 20...
Page 34: ...START UP PL 531 34...
Page 48: ...RECALIBRATION PL 531 48...
Page 56: ...OPERATION PL 531 56...
Page 76: ...PARAMETER DESC PL 531 76...