P080
damping
Sets the speed of response to which the displayed readings
(rate, load and speed), and outputs (alarm and mA) react to change..
Effect of damping (P080) on mA output can be
overridden by mA output damping (P220).
The greater the damping value, the slower the response.
enter damping value, range 1 - 9999
P081
display mode
Sets the display mode. Normally, the display shows rate, or the
last manually selected function. If set to alternating, the display
alternates between rate and totalizer (1 and/or 2, as programmed
by P647).
entry: 0 = normal
1 = alternating
PARAMETER DESC.
PL-531
60