PARAMETER DESCRIPTION
P000
lock
Locks out the programming ’change value’ function such that the values of
P001 through P999 cannot be changed. This however does not prevent the
’select’ function from use; i.e. for viewing values. Programming is locked out
if the value of P000 is other than 1954.
entry: 1954 = unlocked
1954 = locked
Ouick Start, P005 to P017
’Ouick Start ’ is the minimum parameter programming required before
attempting a calibration and successful entry into the run mode.
P005
units
Determines the units for programming and measurement.
entry: 1 = t/h, tonnes per hour
2 = kg/h, kilograms per hour
3 = LT/h, long tons per hour
4 = T/h, short tons per hour
5 = lb/h, pounds per hour
Changing this parameter does not affect the rate (P011), belt speed (P014)
or belt length (P016) parameters. These parameters should be re-entered for
conformity in units.
t = 1000 kg
LT = 2240 lb.
T = 2000 lb.
P011
design rate
Specifies the design rate of material flow for the belt scale.
enter the design rate from the supplied design data sheet
PARAMETER DESC.
PL-531
57