mA output parameters, P200 - P220
These parameters are specific to the use of the mA output.
Refer to Operation \ mA Output for details.
P200
mA range
Sets the range for the mA output.
entry: 1 = 0 - 20 mA
2 = 4 - 20 mA
P201
mA function
Assigns the mA output to track one of the integrator functions.
entry: 1 = rate
2 = load
3 = speed
P212
mA min limit
Limits the lower mA range (0 or 4 mA) to a minimum output value.
enter limit value, range 0 - 22
P213
mA max limit
Limits the upper mA range (20 mA) to a maximum output value.
enter limit value, range 0 - 22
P214
4 mA trim
Adjusts the 4 mA output level to agree with a milliammeter or
other external mA input device.
enter trim value, range 0 - 9999
PARAMETER DESC.
PL-531
62