52
Fault Record
Dec
Hex
Fault Records. Read only. Function 03h or 04h
4096
1000
Fault Record 1
4097
1001
Fault Record 2
:
:
:
:
4145
1031
Fault Record 50
Address
Parameter
Format
Units and
Scale
Range
Each Fault Record consists of 16 words:
Fault record words
Word Number
Description
Format
Units and scale
Range
1
Year
F7
year
0 - 199 (as 2000 - 2199)
2
month, day
F10
month,day
0 - 12, 0 - 31
3
hour, minute
F11
hour, minute
0 - 23, 0 - 59
4
Milliseconds
F7
ms
0 - 59999
5
setting group
F7
--
0 - 1 (as group 1 - 2)
6
source & threshold
See below
source, threshold
0 - 14, 0 - 11
7
Value high word
8
Value low word
9
IL1 high word
10
IL1 low word
11
IL2 high word
12
IL2 low word
13
IL3 high word
14
IL3 low word
15
Io high word
16
Io low word
Word number 6:
High byte: Fault record source code
Bit 0: IL1
Bit 1: IL2
Bit 2: IL3
8: Io
9: Thermal
10: Aux 1
11: Aux 2
12: TCS
13: Remote
14: I2
Low byte: Fault record threshold
0: tI>
1: tI>>
2: tI>>>
3: tIo>
4: tIo>>
5: Thermal Overload
6: tAux 1
7: tAux 2
8: Reserved
9: Reserved
10: Remote trip
11: tI2>
12: tI2>>
13: tIo>>>
0-9.99x10
7
(999kA) or 500-
2000
0-9.99x10
7
(999kA)
0.01 Ampere
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
F8
F8
F8
0.01 Ampere
0-9.99x10
7
(999kA)
0.01 Ampere or 0.1%
thermal