53
Event Record
Dec
Hex
Event Records. Read only. Function 0x03 or 0x04
8192
2000
Record 1
8193
2001
Record 2
:
:
:
:
8441
20F9
Record 250
Alarm Records. Read only. Function 0x03 or 0x04
12288
3000
Record 1
12289
3001
Record 2
:
:
:
:
12317
301D
Record 30
Address
Parameter
Format
Units and
Scale
Range
Each Event or Alarm Record consists of 8 words:
Word Number
Description
Format
Units and scale
Range
1
Year
F7
year
0 - 199 (as 2000 - 2199)
2
month, day
F10
month,day
0 - 12, 0 - 31
3
hour, minute
F11
hour, minute
0 - 23, 0 - 59
4
Milliseconds
F7
ms
0 - 59999
5
Record code
See below
record code
6
Record value
See below
record value
7
Record fault value
8
Record fault value
0-9.99x10
7
(999kA)
F8
0.01 Ampere
Word number 5:
Event and Alarm Record code
0: None
1: I> start
2: tI> trip
3: I>> start
4: tI>> trip
5: I>>> start
6: tI>>> trip
7: Io> start
8: tIo>> trip
9: Io>> start
10: tIo>> trip
11: Remote trip
12: Remote acknowledge
13: Remote reset
14: Setting change
15: Remote thermal state reset
16: Maintenance mode
17: Thermal alarm
18: Thermal overload
19: TCS alarm
20: Group change
21: tAux 1
22: tAux 2
23: tI> reset
24: tI>> reset
25: tI>>> reset
26: tIo> reset
27: tIo>> reset
28: Relay latching
29: Relay unlatching
30: Input activate
31: Input deactivate
32: Idemand alarm
33: General starting
34: Cold load function starting
35: I2> start
36: tI2> trip
37: I2>> start
38: tI2>> trip
39: tI2> reset
40: tI2>> reset
41: Io>>> start
42: tIo>>> trip
43: tIo>>> reset
44: CB Fail
45: Recloser setting error
46: Reclose successful
47: Recloser final trip
48: Recloser locked
49: CB closed by autorecloser
50: Control CB close (input & button)
51: CB remote close
52: CB control open (button)
53: CB Alarm
54: No CB Close Output
55: Inrush blocking
Word number 6:
Event and Alarm Record value
If code is I> start, tI> trip, I>> start,
tI>> trip, I>>> start, tI>>> trip,
Demand alarm:
Bit 0: IL1
Bit 1: IL2
Bit 2: IL3
If code is Setting change:
Value is the register address of
setting being changed
If code is thermal alarm, thermal overload
Value is the % of thermal alarm or
overload threshold:
If code is Group change:
0: group 1
1: group 2
If code is output relay latching, output
relay unlatching:
Bit 0: Output relay 1
Bit 1: Output relay 2
Bit 2: Output relay 3
Bit 3: Output relay 4
If code is input activate, input deactivate:
Bit 0: Input 1
Bit 1: Input 2
If code is tAux 1, tAux 2:
0=Alarm
0x8000=Trip
Word number 7,8:
Fault current value for
tI>,tI>>,tI>>>,tIo>,tIo>>,tIo>>>,tI2>,tI2>>