55
Dec
Hex
Selection of disturbance record and channel. Read only. Function 0x03 or 0x04. Only 1 address being read at a time.
12800
3200
Record number 1, IL1
12801
3201
Record number 1, IL2
12802
3202
Record number 1, IL3
12803
3203
Record number 1, Io
12804
3204
Record number 1, Frequency
12805
3205
Record number 1, Digital input and outputs
13056
3300
Record number 2, IL1
13057
3301
Record number 2, IL2
13058
3302
Record number 2, IL3
13059
3303
Record number 2, Io
13060
3304
Record number 2, Frequency
13061
3305
Record number 2, Digital input and outputs
13312
3400
Record number 3, IL1
13313
3401
Record number 3, IL2
13314
3402
Record number 3, IL3
13315
3403
Record number 3, Io
13316
3404
Record number 3, Frequency
13317
3405
Record number 3, Digital input and outputs
13568
3500
Record number 4, IL1
13569
3501
Record number 4, IL2
13570
3502
Record number 4, IL3
13571
3503
Record number 4, Io
13572
3504
Record number 4, Frequency
13573
3505
Record number 4, Digital input and outputs
13824
3600
Record number 5, IL1
13825
3601
Record number 5, IL2
13826
3602
Record number 5, IL3
13827
3603
Record number 5, Io
13828
3604
Record number 5, Frequency
13829
3605
Record number 5, Digital input and outputs
14080
3700
Record number 6, IL1
14081
3701
Record number 6, IL2
14082
3702
Record number 6, IL3
14083
3703
Record number 6, Io
14084
3704
Record number 6, Frequency
14085
3705
Record number 6, Digital input and outputs
Disturbance record data. Read only. Function 0x03 or 0x04
16384
4000
125 disturbance data words page 1
16385
4001
125 disturbance data words page 2
:
:
:
:
:
:
16523
408B
125 disturbance data words page 140
Address
Parameter
Format
Units and Scale Range
Address: 3200 - 3705
Selection of the disturbance record and channel
Word Number Description
Format
Units and scale
Range
1
No of samples in the mapping
F7
2
Sample number in pre-time
F7
3
Sampling rate
F7
per second
4
Nominal frequency
F7
Hz
0-100
5
Trigger point sample year
F7
year
0 - 199 (as 2000 - 2199)
6
Trigger point sample month, day
F10
month,day
0 - 12, 0 - 31
7
Trigger point sample hour, minute
F11
hour, minute
0 - 23, 0 - 59
8
Trigger point sample milisecond
F7
ms
0 - 59999
9
Phase CT primary current
F7
Ampere
1-10000
10
Earth CT primary current
F7
Ampere
1-10000
11
Phase CT secondary current
F7
Ampere
1-5
12
Earth CT secondary current
F7
Ampere
1-5
13
IL1 channel multiplier
F7
/2048
14
IL2 channel multiplier
F7
/2048
15
IL3 channel multiplier
F7
/2048
16
Io channel multiplier
F7
/8192
All return 0 if record is empty
PC to calculate first sample date and time by using trigger point date_time - pre_time setting.
There are 5 analog and 7 digital channels in the mapping.
No of samples in the mapping: The total samples in the record for each channel.
Phase primary CT ratio applies to IL1,IL2,IL3 channels. Earth primary CT ratio applies to Io channel.
The secondary CT ratio is always 5.
IL1, IL2, IL3, Io channels: The value is signed 16 bits word equivalent to the ADC value
Frequency channel: Measured frequency value x 100Hz.