![Mikro MK 3000L User Manual Download Page 15](http://html1.mh-extra.com/html/mikro/mk-3000l/mk-3000l_user-manual_1793973015.webp)
15
disturbance record current scaling only.
Note: The CT secondary should be connected to 5A or 1A CT input terminal according to the CT
secondary current rating. The display current is calculated by the formula:
Current at CT input terminal / CT input terminal type x CT Pri (setting above)
For example:
Current at CT input terminal = 3A,
CT input terminal type = 5A,
CT Pri = 200A,
The display value = 3/5 x 200 = 120A
Current at CT input terminal = 3A,
CT input terminal type = 1A,
CT Pri = 100A,
The display value = 3/1 x 100 = 300A
Date & Time Menu
Heading of Date & Time menu. Press Enter to enter submenu content.
Displays the date. Press Enter to change the date.
Set the date format for display. Press Enter to change between
DD/MM/YYYY, MM/DD/YYYY.
Displays the time. Press Enter to change the time, starts from hour,
minute and am/pm (if 12 hour format is selected). Second will be reset
to 0 when enter is pressed for any of the digit.
Set the time format. Press enter to change between 12 and 24 hour.
Group Select Menu
Heading of Group Select menu. Press Enter to enter submenu content.
Set whether the protection group setting is change by Menu or Input.
One of the input function must be set to 'Select Group' if Input is
selected. Press Enter to change.
If above is set to Menu, this will set the active protection group. Press
Enter to change.
3.3 Date & Time
Date
18/01/2016
Date Format
DD/MM/YYYY
Time
10:46:23am
Time Format
12-hour
3.4 Group Select
Chg Group by...
Menu
Setting Group
1