9.2 MODBUS Register
*Note: For MK3000L, Device type – main is 00 02 03. Device type –sub is 00.
Dec
Hex
Product information. Read only. Function 03h or 04h
0
0000
F1
ASCII
'00'
1
0001
F1
ASCII
'02'
2
0002
F1
ASCII
'03'
3
0003
Device type - sub*
F1
ASCII
'00'
4
0004
F1
ASCII
'XX'
5
0005
F1
ASCII
'XX'
6
0006
F1
ASCII
'XX'
7
0007
F1
ASCII
'XX'
Measurements and relay status. Read only. Function 03h or 04h
16
0010
Relay status
F2
Bit field
Bit 0 - 15
17
0011
Relay LED status
F3
Bit field
Bit 0 - 11
18
0012
Input status
F4
Bit field
Bit 0 - 3
19
0013
Output status
F5
Bit field
Bit 0 - 4
20
0014
Active group
F6
--
0=group 1, 1=group 2
21
0015
Thermal State
F7
%
0-9999
22
0016
IL1 high word
23
0017
IL1 low word
24
0018
IL2 high word
25
0019
IL2 low word
26
001A
IL3 high word
27
001B
IL3 low word
28
001C
Io high word
29
001D
Io low word
30
001E
IL1 Max high word
31
001F
IL1 Max low word
32
0020
IL2 Max high word
33
0021
IL2 Max low word
34
0022
IL3 Max high word
35
0023
IL3 Max low word
36
0024
Io Max high word
37
0025
Io Max low word
38
0026
IL1 Avg high word
39
0027
IL1 Avg low word
40
0028
IL2 Avg high word
41
0029
IL2 Avg low word
42
002A
IL3 Avg high word
43
002B
IL3 Avg low word
44
002C
Io Avg high word
45
002D
Io Avg low word
46
002E
Line Frequency
F7
0.01 Hz
0-10000 (0-100Hz)
47
002F
I2 high word
48
0030
I2 low word
49
0031
Relay status 2
F25
Bit field
Bit 0-2
50
0032
CB Opening Time
F7
ms
0-65535 (65.535s)
51
0033
CB Closing Time
F7
ms
0-65535 (65.535s)
52
0034
CB Operations high word
53
0035
CB Operations low word
54
0036
∑
Α
mps(n) I1 high word
55
0037
∑
Α
mps(n) I1 low word
56
0038
∑
Α
mps(n) I2 high word
57
0039
∑
Α
mps(n) I2 low word
58
003A
∑
Α
mps(n) I3 high word
59
003B
∑
Α
mps(n) I3 low word
Remote command. Write only. Function 06h
256
0100
Remote Command
F9
Bit field
--
Settings. Read/Write. Function 03h, 04h, 06h, 10h
512
0200
Phase CT Primary
F7
Ampere
1 - 10000
513
0201
Phase CT Secondary, In
F6
Ampere
0=1, 1=5
514
0202
Earth/Ground CT Primary
F7
Ampere
1 - 10000
515
0203
Earth/Ground CT Secondary, Ion
F6
Ampere
0=1, 1=5
516
0204
Frequency
F6
--
0=50Hz, 1=60 Hz
517
0205
Time Window for Average and Maximum Current
F7
minute
1 - 60
518
0206
Year
F7
year
0 - 199 (as 2000 - 2199)
519
0207
month, day
F10
month,day
0 - 12, 0 - 31
520
0208
hour, minute
F11
hour, minute
0 - 23, 0 - 59
521
0209
Milliseconds
F7
ms
0 - 59999
Address
Parameter
Format
Units and Scale Range
Device type - main*
Version number -main
Version number -sub
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
0.01 Ampere
0-9.99x10
7
(999kA)
F8
--
0-99999
F8
Ampere
0-4000x10
6
(4000MA)
F8
Ampere
0-4000x10
6
(4000MA)
F8
Ampere
0-4000x10
6
(4000MA)