22
Set the dead time for reclose cycle 3.
Set the dead time for reclose cycle 4.
Set the reclaim time.
. The reclaim time starts when the CB has closed
(52A input activates). If no tripping after reclaim time elapsed, the
autoreclose resets.
Set the inhibit time. This timer is used to block the autoreclose being
initiated after lockout and CB is manually closed onto a fault.
Set the number of shots for phase cycle. Applies to tI>, tI>>, tI>>>,
tAux 1 and tAux 2
Set the number of shots for earth fault. Applies to tIo>, tIo>> and
tIo>>>
Set the actions to be executed for each cycle associated to the trip or
start for each element.
0: Recloser will move to lock status after tripping.
1: Tripping, followed by reclose cycle.
2: No trip or pickup.
PROTECTION G2 Menu
5.PROTECTION G2 (Group 2) menu has similar content as PROTECTION G1 (Group 1) menu.
The Protection G2 settings are applied when Protection Group 2 is activated.
INPUT Menu
Heading of INPUT menu. Press Enter to enter submenu content.
6.INPUT
Dead Time
tD3 6.00s
Dead Time
tD4 10.00s
Reclaim Time
tR 8.00s
Inhibit Time
tI 20.0s
Phase Cycles
3
Earth Cycles
2
CYCLES 1 2 3 4
tI>
0
1 1 1
tI>>
1 1 1 1
tI>>>
1 1 2 1
tIo>
1 1 1 1
tIo>>
0
1 1 1
tIo>>>
1 1 1 2
tAux 1
0
0 1 1
tAux 2
0
0 1 1