25
Output Relay 2 to 4
Output Relay 2 to 4 menu has similar content. The output Relay 2 menu content is shown below:.
Heading of output Relay 2 menu. Press Enter to enter submenu
content.
If relay function is set to Trip, the menu content similar to Relay 1 is shown, please refer to
Output Relay 1.
If relay function is set to Start/Other, the following menu is displayed:
tI>>>?
Yes
Assign I>>> trip to the output relay.
tIo>?
Yes
Assign Io> trip to the output relay.
tIo>>?
Yes
Assign Io>> trip to the output relay.
tIo>>>?
Yes
Assign Io>>> trip to the output relay.
Thml OL?
Yes
Assign Thermal Overload to the output relay.
tAux 1?
Yes
Assign Aux 1 input trip to the output relay.
tAux 2?
Yes
Assign Aux 2 input trip to the output relay.
Remote
Yes
Assign Remote trip (by communication and
Open CB
control) to the
output relay
tI2>?
Yes
Assign I2> trip to the output relay.
tI2>>?
Yes
Assign I2>> trip to the output relay.
Relay 2 Func Trip
Set the function of output Relay 2. Possible settings are: Trip,
Start/Other and CBFP .
Reset
Auto
Set the reset method of relay: Auto (Unlatched), Manual (Latched).
I>?
Yes
Assign I> start to the output relay.
I>>?
Yes
Assign I>> start to the output relay.
I>>>?
Yes
Assign I>>> start to the output relay.
Io>?
Yes
Assign Io> start to the output relay.
Io>>?
Yes
Assign Io>> start to the output relay.
Io>>>?
Yes
Assign Io>>> start to the output relay.
Thml OL(Alarm)? Yes
Assign Thermal Overload Alarm to the output relay.
7.2 Relay 2