Chapter 4: Using the Command Line Interface
156
Note: Power-on sequencing is disabled in the latching mode. Refer to
PDU Latching Relay Behavior
in the PDU
www.middleatlantic.com/resources/power-downloads.aspx
Setting the Outlet Power-On Sequence Delay
This command sets the delays (in seconds) for outlets when turning on all outlets in sequence.
config:#
pdu outletSequenceDelay <outlet1>:<delay1>;<outlet2>:<delay2>;
<outlet3>:<delay3>;...
Separate outlet numbers and their delay settings with a colon. Outlets followed by delays are separated with a semicolon.
Variables:
•
<outlet1>, <outlet2>, <outlet3> and the like are individual outlet numbers or a range of outlets using a dash. For
example,
3-8
represents outlets 3 to 8.
•
<delay1>, <delay2>, <delay3> and the like are the delay time in seconds.
Note: Power-on sequencing is disabled in the latching mode. Refer to
PDU Latching Relay Behavior
in the PDU
www.middleatlantic.com/resources/power-downloads.aspx
Setting the PDU-Defined Default Outlet State
This command determines the initial power condition of all outlets after powering up the PDU.
config:#
pdu outletStateOnDeviceStartup <option>
Variables:
•
<option> is one of the options:
off
,
on
or
lastKnownState
.
Option
Description
off
Switches OFF all outlets when the PDU powers up.
on
Switches ON all outlets when the PDU powers up.
lastKnownState
Restores all outlets to the previous status before powering down the device when the PDU
powers up again.
Note: This feature does NOT take effect and cannot be configured on a PDU after the outlet relay is set to the "Latching"
mode. Refer to
PDU Latching Relay Behavior
in the PDU With RackLink User Manual at