Chapter 4: Using the Command Line Interface
156
After performing the above command, the PDU prompts you to confirm the operation. Press
y
to confirm or
n
to abort the
operation.
To skip the confirmation step, you can add the "/y" parameter to the end of the command so that the operation is executed
immediately.
#
loadshedding <option> /y
Variables:
•
<option> is one of the options:
enable
or
disable
.
Option
Description
start
Enter the load shedding mode.
stop
Quit the load shedding mode.
Example
The following command puts the PDU into load shedding mode.
config:#
loadshedding start
Power Control Operations
Outlets on the PDU can be turned on or off or power cycled through the CLI.
Besides, you can cancel the power-on process while the PDU is powering on ALL outlets.
You must perform this operation in the
administrator mode
Different CLI Modes and Prompts
(on page 20).
Turning On the Outlet(s)
This command turns on one or multiple outlets.
#
power outlets <numbers> on
To quicken the operation, you can add the parameter "/y" to the end of the command, which confirms the operation.
#
power outlets <numbers> on
/y
Variables:
•
<numbers> is one of the options:
all
, an outlet number, a list or a range of outlets.
Option
Description
all
Switches ON all outlets.