12
Service Manual
www.microphase.eu
Dc
Fault drive, open collector output max. 50mA
Normally closed, opens when the drive in protection mode
2.2
FAULT output
(Signal terminal pin 2)
DRIVE
2.1
Current monitor output
DRIVE
Multimeter
1,27
Standard product is set to the signal CURR on terminal 1 (reading of the current circulating on the
motor) and the REQ input at terminal 3.
Note:
On this terminal is available analog output "current monitor of motor" with range 0V + /-8V. The value
of 8V is the maximum current supplied by the drive. For example, if we have a size 7/14A, 8V
corresponds at 14A circulating on the motor.
The signal can be positive or negative depending on the direction of rotation of the motor.
Output Impedance is 10Kohm. Consider the internal impedance in the case are linked external
resistive divider.
(Signal terminal pin 1)