U1000MKII User Manual
Micronics
Page 44
Issue 3.1 July 19
6
APPENDIX
6.1
Specification
General
Measuring Technique
Transit time
Measurement channels
1
Timing Resolution
±50ps
Turn down ratio
200:1
Flow velocity range
0.1 to 10m/s
Applicable Fluid types
Clean water with < 3% by volume of particulate content, or up to
30% ethylene glycol.
Accuracy
±3% of flow reading for velocity rate >0.3m/s
Repeatability
±0.15% of measured value
Pipe Ranges
25-115mmOD and 125-180mm OD
Note: Pipe size is dependent on pipe material and internal diameter.
Selectable units for metric (mm)
Velocity: m/s
Flow Rate: l/s, l/min, m
3
/min, m
3
/hr
Volume: litres, m
3
Selectable units for Imperial
(inches)
Velocity: ft/s
Flow rate: gal/min, gal/hr, USgal/min, USgal/hr
Volume: gals, USgals
Totaliser
14 digits with roll over to zero
Languages supported
English only
Power input
12
–
24V DC or 24V AC
Power consumption
7W (DC) or 7VA (AC) maximum
Cable
5m screened 6 core
Pulse Output
Output
Opto-isolated MOSFET volt free contact (NO/NC).
Isolation
1MΩ @ 100V
Pulse width
Default value 50ms; programmable range 3
–
99ms
Pulse repetition rate
Up to 166 pulses/sec (depending on pulse width)
Frequency mode
200 Hz maximum (Range 1-200)
Maximum load voltage/current
24V DC or 24V AC / 500mA
Current Output
U1000MkII-FM only
Output
4
–
20mA
Resolution
0.1% of full scale
Maximum load
620Ω
Isolation
1MΩ @ 100V
Alarm current
3.5mA
continued on next page