Micronics
U1000MKII User Manual
Issue 3.1 July 19
Page 41
SEND_UD
–
SET BAUD RATE 9600
COMMAND:
SEND_UD
–
SET BAUD RATE 9600
DESCRIPTION:
Sets the slave data rate to 9600 baud. The slave responds to the
request with ACK at the current baud and then modifies its baud
setting. If the slave does not receive a message from the master at
the new rate within 2 minutes, the slave defaults to a setting of 300
baud.
DIRECTION:
MASTER TO SLAVE
FRAME TYPE:
CONTROL / LONG FRAME
PRIMARY ADDRESSING
SECONDARY ADDRESSING
NAME
CODE
NAME
CODE
START
0x68
START
0x68
LENGTH
0x03
LENGTH
0x0B
LENGTH
0x03
LENGTH
0x0B
START
0x68
START
0x68
(C - FIELD)
SEND_UD
0x73
(C - FIELD)
SEND_UD
0x73
(A - FIELD)
SLAVE PRIMARY ADDRESS
0xXX
(A - FIELD)
USE SECONDARY
ADDRESSING
0xFD
(CI
–
FIELD)
SET BAUD RATE 9600
0xBD
(CI
–
FIELD)
SET BAUD RATE 9600
0xBD
CHECKSUM
0xXX
M-Bus IIN (BYTE 1)
0xXX
STOP
0x16
M-Bus IIN (BYTE 2)
0xXX
M-Bus IIN (BYTE 3)
0xXX
M-Bus IIN (BYTE 4)
0xXX
MANF. ID (BYTE 1)
0xCD
MANF. ID (BYTE 2)
0x54
VERSION NUMBER
0x01
DEVICE TYPE ID
0x04
CHECKSUM
0xXX
STOP
0x16
MASTER TO SLAVE: SEND_NKE
SLAVE TO MASTER: ACK
MASTER TO SLAVE: SEND_UD
–
SET 9600 BAUD
SLAVE TO MASTER: ACK