Chapter 3: Operation
3-LV-1-7 9/7/11
LV1 User Manual
3-7
2.
Using the funnel and tube supplied in the tool kit, begin to slowly pour approximately
0.4 gallon (1.5 liters) slowly into the hydraulic reservoir.
3.
Replace the fill/vent cap.
4.
Operate the unit in
JOG
mode by retracting and extending the piston fully for 5-10
strokes in order to remove air in the hydraulic system.
5.
Remove the fill/vent cap and with the unit in the turned off position, check the oil
level. The oil level should be between 1-1/2 to 1 inch from the top of the fill hole.
NOTE:
The hydraulic system capacity is approximately 0.7 gallons (2.5 liters). When the unit is
readied for shipment, the hydraulic oil is evacuated using hand pump part #10.3425 and
approximately 0.26 gallons (1 liter) are left in the system. This is why the customer must
fill the hydraulic oil reservoir with approximately 0.4 gallons (1.5 liters) prior to starting
the unit.
Environmental Requirements
Temperature
Do not place the Microfluidizer equipment in an area where the ambient temperature is above
86ºF (30ºC) or below 50ºF (10ºC). Refer to the Duty Cycle section for more information.
Ventilation Requirements
The Microfluidizer equipment dissipates heat to the surrounding environment. The customer must
provide adequate ventilation.
Preparing Utility Hookups
Connect the power cord to a 10 or 5 Amp, 110V or 208-230VAC, 50 or 60 Hz power outlet. Remove
the lockout device on the Master Power on/off switch using small, flat-blade screwdriver.
NOTE:
For the seal quench option, use a separate source of water. See Appendix C: Options for
more detailed information on the piston seal quench option.
CAUTION: CUSTOMERS SHOULD NOT START THE MOTOR WITHOUT ENSURING THAT A
SUFFICIENT LEVEL OF OIL IS IN THE TANK. DAMAGE TO THE PUMP AND HYDRAULIC SYSTEM
COULD RESULT.
General
The LV1 you have purchased (or rented or leased) is carefully engineered, manufactured,
inspected, and tested. Nevertheless, the use of the equipment involves the handling of fluids at
high pressure. Therefore, certain precautions must be taken. DO NOT proceed with this chapter
until you read and understand the introduction and have completed the necessary installation
requirements.
NOTE:
For all of the following procedures, before you start, be sure you have done the following: