Page 12
optoCONTROL 1202
Model
optoCONTROL 1202-75
optoCONTROL 1202-100
LED-indication
LED red (+): Measuring value > upper tolerance threshold
LED green: Measuring value lies within tolerance threshold
LED red (-): Measuring value < lower tolerance threshold
LED yellow: multifunction
Protection class
electronics: IP 54, optics: IP 67
Shock
15 g / 6 ms
Vibration
15 g / 10 Hz…1 kHz
Operating temperature
-10 to +50 °C (+14 to +122 °F)
Storage temperature
-20 to +85 °C (-4 to +185 °F)
Output
Analog
0 …+10V (scalable)
Digital
OUT0, OUT1, OUT2: pnp-bright-switching/npn-dark-switching or
pnp-dark-switching/npn-bright-switching, adjustable under Windows,
max. 100 mA, short-circuit proof
Digital input
IN0
external trigger, input vUb/0 V with protective circuit
IN1
teach/Reset, input vUb/0 V with protective circuit
Power supply
+15 VDC … + 30 VDC, typ. 200 mA
Sensitivity adjustment
using Windows via PC (parameterization software included)
Laser adjustment
adjustable using Windows via PC
The quoted technical data apply for a displacement light source to receiver about 300 mm and a temperature
of 20 °C (+68 °F) after a warm-up time of 30 minutes.
1) Display resolution of the software ≤ 10 µm
2) Valid for ΔT≤5°C and ambient light 5000 lx. For stable measurement shadowing of the receiver is
advisable. Smooth video AVG 64 values.
3) Is only valid with the adaption of the THD threshold and the laser performance as well as the execution of
an calibration; 20 mm target-receiver distance; 250 mm transmitter-receiver distance
4) Laser class 1: IEC 60825-1: 2008-05
5) Shadowing from ambient daylight increases the signal stability