5.1.2  Choice 2: UPS parameters

The blue lines are those displayed on screen.

+============================================================================+

|                         [ UPS Parameters Menu ]                            |

+============================================================================+

SNMP/Web Agent Version            : CAb8 (SN 49DC40116)

Ethernet address                           : 00 E0 D8 09 85 78

Agent BIOS Version                      : AB

1. Log Periodicity                           : 60

Value between 20 and 99999. Enables initialisation of the save frequency of Measurements, Events and

System in the Log menu. Default value = 60 sec.

2. Trap Port Number                          : 162

Numeric field limited to 65534. Enables forwarding of the traps sent by the card to a port other than the one

usually used for SNMP. Default value 162

3. System Date (yyyy/mm/dd)           : 2003/06/10

Enables adjustment of the date

4. System Time (hh:mm:ss)              : 14:47:53

Enables adjustment of the time

0.  Return to previous menu

5.1.3  Choice 3: Access control

+============================================================================+

|   IP Address       Community String      Access                            |

+============================================================================+

[1] 0.0.0.0          public                NotAccess

[2] 0.0.0.0          public                NotAccess

[3] 0.0.0.0          public                NotAccess

[4] 0.0.0.0          public                NotAccess

Summary of Contents for Environment Sensor 66846

Page 1: ...Network Management Cards User Manual T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Network Management Card User Manual 34003676EN BB Page 1 76 Minislot 66244 Transverse 66074 Environme...

Page 2: ...________ 10 1 8 1 Configuration ________________________________________________________________ 10 1 8 2 Administration________________________________________________________________ 10 1 8 3 Networ...

Page 3: ...______________________________________ 31 3 5 CONFIGURATION __________________________________________________________________ 33 3 5 1 Network Settings _______________________________________________...

Page 4: ...______________ 65 5 1 4 Choice 4 Restore default configuration____________________________________________ 66 5 1 5 Choice 5 Reset the card _______________________________________________________ 66 5...

Page 5: ...n provides information on events concerning the supply of power to the computers connected to your computer network carries out automatic shutdown of computer systems monitors and controls all the UPS...

Page 6: ...cket Layer SSL with the Proxy and the XML Web Card 1 1 2 Protecting the computers servers This function is performed by the Network Shutdown Module installed on each of the servers to be protected Not...

Page 7: ...omputers to be protected by the UPS Connect the UPS to a wall outlet For UPSs above 3kVA please refer to the UPS installation manual Connect the power cord of each computer to an outlet on the UPS For...

Page 8: ...work Management Cards acquire information on the operation status of the UPS systems and provide remote control of these systems by means of an ETHERNET network from any SNMP administration station or...

Page 9: ...er HP Insight Manager The Management Pac 2 offering includes the necessary SNMP plug in to allows an easy integration in the NMS Events are notified by SNMP trap NMS can subscribe on page Notified App...

Page 10: ...shutting down the installation Control of UPS on off switching via the HTML interface Adjustment and control of PowerShare outlets via the HTML interface sequential starting of the installation and o...

Page 11: ...rature readings in Celsius or Fahrenheit High and low thresholds hysteresis and offset adjustable via Web interface Possibility of notification of status changes by e mail SMS or SNMP traps Position d...

Page 12: ...m web site in the Download area embedded Software section 2 1 Installation 2 1 1 Installing the card in the UPS 2 1 2 Connecting the card to the IT network 2 1 3 Understanding front panel signals 2 2...

Page 13: ...omputer equipped with a Web browser Internet Explorer or Netscape recommended enter the address initialised previously in the Installation chapter e g http 213 30 17 30 The UPS properties home page is...

Page 14: ...e 14 76 3 2 UPS 3 2 1 UPS properties page This page gives instant access to the essential information about your UPS This page is automatically refreshed every 10 seconds by default To change this val...

Page 15: ...PS and the Network Shutdown Card in particular the model range and software version Note If the UPS is connected by dry contacts neither picture or name are indicated the 2 contacts title is displayed...

Page 16: ...er output indicates if the UPS output is protected Controlled outlets indicates if the controlled outlets if available are powered 3 2 1 3 Battery status zone Bargraph Graph showing the remaining batt...

Page 17: ...g to Unsubscribe This window can be closed whenever you wish As soon as a new event occurs on the UPS it is re opened automatically as long as your browser remains open To stop subscription click on t...

Page 18: ...gement Card User Manual 34003676EN BB Page 18 76 3 2 2 On line help On line contextual help in French or English is available at the top of each page by clicking on the Help link which is always locat...

Page 19: ...s The status of each output is displayed by a symbol associated with the Off label red symbol or Powered green symbol The shutdown sequences take into account the time required for the registered serv...

Page 20: ...the end of the time delay specified in the Toggle duration parameter The output status is updated Immediate On a sequence to switch on output power is launched immediately The output is re powered an...

Page 21: ...operly run Read the UPS manual for more information The weekly schedule enables the administrator to optimise power consumption or program a reboot of the protected equipment at a set time In a shutdo...

Page 22: ...up periods the card will send a command to the UPS to shut off end of the programmed Shutdown After time To prevent this a value greater than the maximum installation backup time must be programmed Th...

Page 23: ...t is thus possible to limit repeated restarts that may be due to several successive utility failures If the Battery is charged for and If Capacity exceeds are two extra conditions for minimum battery...

Page 24: ...P R O V I D E R Network Management Card User Manual 34003676EN BB Page 24 76 3 2 6 Viewing the alarms Click on the Alarm table section in the menu to view the list of current alarms The table of manag...

Page 25: ...ge of the 3 phases for UPS with a 3 phase output Output load Value of the percentage of load at UPS output Value of the most loaded phase for 3 phase UPS Battery capacity Percentage of charge availabl...

Page 26: ...w mgeups com Network Management Cards User Manual T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Network Management Card User Manual 34003676EN BB Page 26 76 Select the time range to vi...

Page 27: ...3 3 2 Event log Click in the Event log section of the menu Save Log enables all values saved to be opened or saved in CSV format compatible with Excel type spreadsheets Clear Log enables deletion of...

Page 28: ...6 3 3 3 System log Click in the System log section in the menu Save enables all values saved to be opened or saved in CSV format compatible with Excel type spreadsheets Clear enables deletion of all r...

Page 29: ...mails is compatible with mobile telephone transfer systems using text messages SMS Notified events The left side of the page shows the events that can be notified By default only the main events of ba...

Page 30: ...t Periodic report In addition to the e mails sent when events occur a periodical e mail containing the 4 log files can be sent to the recipient every x days at the time specified by the user To config...

Page 31: ...domain com This field is free However depending on the type of SMTP server configuration it is possible that the server checks that the domain name contained in the From address exists and even that t...

Page 32: ...Card User Manual 34003676EN BB Page 32 76 The body of the e mail sent is composed of Message text which is free text the date and time of the event as saved in the log URL of the card enabling a dire...

Page 33: ...cters max After entering the login and password these identifiers remain active as long as the browser is open so you only have to enter them once If the browser is closed they will have to be re ente...

Page 34: ...rd e g 172 17 23 205 Subnet Mask The mask of the sub network of your network e g 255 255 255 0 Gateway Address Indicate the IP address of the gateway to access the stations located outside the card s...

Page 35: ...te upgrading of the embedded system on the card using the Mupgrade tool Read the Maintenance section for more details Primary DNS server contains the IP address of the main DNS server ensuring convers...

Page 36: ...tion limited to 32 characters of the location of the UPS in your installation e g Computer room E1 C066 This text is displayed on the home page at the top right above the name of the UPS Its value by...

Page 37: ...0 to 9 sec Period during which a status change by one of the inputs is not considered Default value 1 sec only visible if the sensor is present Reset communication button performs a remote reboot of...

Page 38: ...s Simulate events to test notification and shutdown of the Notified Applications Up to 50 destinations can be managed by the card The card is compatible with the Network Shutdown Module and with the l...

Page 39: ...unch of the shutoff sequence of the UPS This parameter is optionnal Many actions are available on this page Remove Depending on the kind of application the selected ones will definitively disappear fr...

Page 40: ...34003627zjaa pdf available in the Embedded zone of the www mgeups com site 3 5 4 Central Shutdown Configuration Click the Notified Application section in the menu then in Configuration This page is u...

Page 41: ...f the shutdown timer the shutdown procedure is immediately run This parameter is optional uncheck it to invalidate Shutdown Duration This is the time in seconds required by the system to go through it...

Page 42: ...limited to 10 characters Enables secure access and modification of pages Default value MGEUPS Enter New Password Text field limited to 10 characters Enables secure access to the sections of the Confi...

Page 43: ...r Manual 34003676EN BB Page 43 76 Change Community Read Write Text field limited to 31 characters This field is only validated after clicking on Save Default value public Change Trap Port Number Numer...

Page 44: ...ues entered in the Date and Time fields Values are updated after clicking the Save button Synchronise with computer time Enables the date and time of your PC to be transferred to the card This transfe...

Page 45: ...Settings port of the Network Management Card On startup the card automatically detects sensor presence The main menu then displays an additional section Environment with the following elements Status...

Page 46: ...both measurements a graduated gauge proposes the following functions The cursor indicates the current value Two red zones to the left and right represent the high and low thresholds that can be set o...

Page 47: ...atus change of each contact is time stamped The Internet browser updates this page regularly according to the Environment refresh rate parameter on the System settings page 3 6 3 Environment Settings...

Page 48: ...exceeded a notification is sent if enabled Default value is 5 Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold Default value is 5 Advanced parameters...

Page 49: ...and Humidity are recorded at an interval defined by the Environment log interval parameter on the System settings page By default this period is 300 seconds Each measurement is dated and stored in the...

Page 50: ...Notified Applications 4 1 1 Shutdown criteria managed by the Management Card During an extended power failure three criteria may cause the server shutdown procedure to be initiated If several criteria...

Page 51: ...in seconds 4 1 2 Specific set up for long autonomy installation 30 mn On installation where the backup period is longer than 30 minutes the Network Management Card will initiate automatically a shutd...

Page 52: ...time by shutting down non priority equipment or sequencing the shutdown of several devices Two shutdown criteria are possible Shutdown of outlets after a set battery back up time ShutOff Delay Shutdow...

Page 53: ...rs is initiated followed by the UPS shutdown depending on its configuration The UPS restarts when utility power is restored depending on its configuration Shutdown Duration Maximum value of shutdown t...

Page 54: ...when utility power is restored possibility of programming a restart delay Utility Trap 17 Trap 11 Trap 29 ShutdownTimer Trap 18 Trap 31 Shutdown Duration Trap 32 NSM UMC Shutdown Reboot Main outlet 4...

Page 55: ...nagement Card User Manual 34003676EN BB Page 55 76 4 2 1 3 Programmable outlet 2 Shuts down after Shutoff Delay 2 after having stopped the servers Restarts when utility power is restored by applying R...

Page 56: ...wn after taking into account the shutdown duration of the servers Low battery power The message appears if either of the two following criteria is checked Low Battery Level Minimum remaining backup ti...

Page 57: ...U N I N T E R R U P T I B L E P O W E R P R O V I D E R Network Management Card User Manual 34003676EN BB Page 57 76 4 2 2 3 Programmable outlet 2 Trap 29 ShutoffTimer 2 Restart Delay 2 Trap 31 Sh do...

Page 58: ...the Shutdown Duration If utility power is restored before the end of the Shutdown Duration the UPS is shut down after the Shutdown Duration for a period equal to the forced reboot time delay 4 2 3 1 M...

Page 59: ...U N I N T E R R U P T I B L E P O W E R P R O V I D E R Network Management Card User Manual 34003676EN BB Page 59 76 4 2 3 3 Programmable outlet 2 Trap 29 ShutoffTimer 2 Restart Delay 2 Trap 31 Shutd...

Page 60: ...nd Off On command is sent from the UPS control page 4 2 4 1 Main outlet Utility Off command with a shutdown delay 2 minutes 2 minutes On command with a restart delay 0 minutes Trap 29 Trap 31 Shutdown...

Page 61: ...U N I N T E R R U P T I B L E P O W E R P R O V I D E R Network Management Card User Manual 34003676EN BB Page 61 76 4 2 4 3 Programmable outlet 2 Trap 29 ShutoffTimer 2 Restart Delay 2 Trap 31 Shutd...

Page 62: ...ld be set at 9600 bauds 8 bits no parity 1 stop bit and no flow control Check that UPS power is on A few seconds after terminal opening press the Enter button The menu asks you to enter your password...

Page 63: ...n AB Version number of the BIOS 1 IP Address 172 17 133 120 To change the IP address of the card press 1 then Enter Specify an IP address then press Enter 2 Gateway Address 172 17 1 1 Enter the name o...

Page 64: ...Username MGEUPS Text field limited to 10 characters Enables secure access to the sections of the Configuration menu Default value MGEUPS a Manager Password Text field limited to 10 characters Enables...

Page 65: ...Enables initialisation of the save frequency of Measurements Events and System in the Log menu Default value 60 sec 2 Trap Port Number 162 Numeric field limited to 65534 Enables forwarding of the trap...

Page 66: ...ure corresponding to the command to be carried out then the number of the target input The example below shows how to configure the read write rights for a station 172 17 1 1 with a community name MyC...

Page 67: ...5 2 Configuration via Telnet You can access the configuration menu see configuration in local mode section from a station equipped with the Telnet protocol As soon as the card is accessible on the net...

Reviews: