Network Management Card
– User Manual
34003676EN/BB
Page
23/76
Note
Priority is given to the main outlet, so the card does not accept configurations where the auxiliary outlets can be
supplied while the main outlet is switched off
For the main outlet (Master)
◗
Shutdown after
is the operating time in minutes left for users after a switch to backup before starting
the shutdown sequences of the UPS and its equipment (from 0 to 1092).
◗
If remaining time under
(from 0 to 9999 seconds) and
If Capacity under
(from 0 to 100%) are two
extra conditions for remaining backup time and battery level that can trigger shutdown sequences
before the “
Shutdown after
” period runs out
◗
Shutdown duration
is the time required for complete shutdown of systems when a switch to backup
time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum
of Shutdown duration of subscribed clients but can be modified in the Advanced mode
◗
Restart after
is the minimum shutdown time before restarting the UPS after a shutdown sequence. It is
thus possible to limit repeated restarts that may be due to several successive utility failures.
◗
If the Battery is charged for
and
If Capacity exceeds
are two extra conditions for minimum battery
level and maximum recharge time to be reached before restarting the UPS after utility restoration
For controlled outlets (group 1 or group 2 ), the page enables programming of operation time and level in
backup mode to manage outlet load shedding in the event of electric power failure:
◗
Switch Off after
defines the time during which the outlet is supplied starting from the moment of utility
failure. Caution, this time includes the outlet shutdown duration.
◗
Switch Off if capacity under
is an extra condition for outlet shutdown that can trigger the shutdown
sequence before shutdown duration runs out.
◗
Shutdown duration
is the time required for complete shutdown of the systems supplied by the outlet
when an outlet shutdown sequence is launched.
It is calculated automatically using the maximum shutdown durations of subscribed clients.
◗
Switch On
is the period between main output startup and startup of the relevant programmable outlet,
therefore outlet startup can be delayed in relation to the main output.
Security:
The administrator has to click on
Save
and enter his login/password to save any modifications. The
default login and password are
: MGEUPS