T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Card
– User Manual
34003676EN/BB
Page
19/76
3.2.3 UPS
Control
Click on the
“UPS Control”
section in the menu.
If the UPS is not compatible with this function, a warning message is sent to the user.
UPS configuration may also prevent the commands from being properly run. Read the UPS manual for more
information.
This page enables triggering of
startup and shutdown sequences
for the UPS’ main output and Controlled
outlets.
◗
The status of each output is displayed by a symbol associated with the
Off
label (red symbol) or
Powered
(green symbol).
◗
The shutdown sequences take into account the time required for the registered servers to shut down
without losing data (
see shutdown parameters
). Once the sequence has started, the commands are
disabled until it ends.
◗
After a startup sequence, the commands are disabled for 120 seconds to enable the servers to restart fully
◗
The main outlet has priority over the auxiliary outlets. Shutdown of the main outlet causes the auxiliary
outlets to shut down. Auxiliary outlets can only be started if the main outlet is powered
The Check column proposes six different commands, and a command is only actually started after clicking on
'Execute'
: