www.mgeups.com
Network
Management Cards
User Manual
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Card
– User Manual
34003676EN/BB
Page
41/76
◗
Shutdown After (time before shutdown)
This is the time in seconds that the system waits following
failure of AC power before initiating the system-shutdown procedure. This value must be selected to
provide users with enough time to close their applications and disconnect, but within the battery backup
time provided by the UPS.
If another criterion occurs before the end of the shutdown timer, the shutdown procedure is immediately
run.
This parameter is optional, uncheck it to invalidate
◗
Shutdown Duration
: This is the time in seconds required by the system to go through its shutdown
procedure.
◗
Broadcast
: Send network notifications to the Administrators and Users groups on events
If you wish to set up a new configuration for the Network Shutdown Modules already set to centralized-
configuration mode, proceed as indicated below.
◗
Change the Network Shutdown Module parameters in the page “Central Shutdown Configuration”.
◗
Click the
Save
button. Open the List of notified applications.
Select the Network Shutdown Modules to receive the new configuration.
Press the button “
Remove”
They reconnect and use the new configuration