TROUBLE SHOOTING
Mechanical/electrical defects
1. A change in the valve position setpoint will not affect the
position of the actuator
Supply pressure too low
Spool valve sticks
Incorrect configuration parameters
Actuator and/or valve jammed
Signal wires incorrectly connected, no value on dis-
play
Circuit boards are defective
Calibration has not been carried out
Device is in manual mode
Prestage is defective
Device is in fail-safe mode
Spool mounted backwards into spool valve
2. Inaccurate positioning
Spool valve dirty
Too high actuator load
Supply pressure too low
Spool or pressure sensors are defective
Actuator leakage
3. Overshooting or positioning too slow
Spool valve dirty
Supply air tube too small or supply air filter dirty
Valve sticks
Check leakages in tubes between controller and
actuator
Check leakages in mechanical stop screws
Check correctness of MAXS parameter. Change it
from "slow" to "fast" or "moderate".
4. Error during valve travel calibration
Valve controller is in
MAN
mode
Check the coupling alignment with the pointer, see
Fig. 3
The parameter setting
PFA
incorrectly selected
The actuator or valve did not move or was stuck dur-
ing calibration
Supply pressure too low
Spool valve dirty
Display message
Description
CALIBRATION FAILED
Calibration process has failed.
CALIBRATION START FAILED
Calibration process could not be
started.
CALIBRATION TIMEOUT
Calibration process has taken too
long time.
FACTORY SETTINGS CREATE FAIL
Factory settings creation failed.
FACTORY SETTINGS RESTORE FAIL
Factory settings restoration failed,
i.e. current parameter set could not
be loaded with factory settings.
INTERNAL BOOT RESET
Software has lost the control and
internal watchdog generated reset.
POSITION SENSOR FAILURE
Position sensor defect has been
detected.
POSITION SENSOR RANGE ERROR
Too narrow position sensor range
was detected in position
calibration process.
PRESSURE SENSOR 1 FAILURE
Pressure sensor #1 defect has been
detected.
PRESSURE SENSOR 2 FAILURE
Pressure sensor #2 defect has been
detected.
PRESSURE SENSOR 3 FAILURE
Pressure sensor #3 defect has been
detected.
PRESTAGE CUT ERROR
Prestage coil cut has been
detected.
PRESTAGE SHORTCUT ERROR
Prestage coil shortcut has been
detected.
PT COMMUNICATION ERROR
Communication with position
transmitter was lost.
STATISTICS DATABASE ERROR
Error occurred when writing
statistics to database.
TEMPERATURE SENSOR FAILURE
Temperature sensor defect has
been detected.
Display message
Description
ACTUATOR FULL STROKES
WARNING
Actuator full stroke counter has
exceeded the warning limit.
CLOSE STROKE DEVIATION
WARNING
Valve close stroke deviation time
trend has exceeded the warning
limit.
OPEN STROKE DEVIATION
WARNING
Valve open stroke deviation time
trend has exceeded the warning
limit.
REDUCED PERFORMANCE
ACTIVATED
Controller can not perform
boosting due to pressure sensor
failure. Also, position sensor failure
cause device to act like any normal
solenoid device: position can not
be controlled.
SPOOL REACTION TIME CLOSE
WARNING
Spool valve reaction time close
trend has exceeded the warning
limit.
SPOOL REACTION TIME OPEN
WARNING
Spool valve reaction time open
trend has exceeded the warning
limit.
SUPPLY PRESSURE OUT OF LIMITS
Supply pressure is out of warning
limits.
SUPPLY PRESSURE TREND
WARNING
Supply pressure trend value has
exceeded the warning limits.
TEMPERATURE OUT OF LIMITS
Temperature is out of warning
limits.
TEMPERATURE TREND WARNING
Temperature trend value has
exceeded the warning limits.
TOTAL OPERATION TIME WARNING
Total operating time has exceeded
the warning limit.
VALVE FULL STROKES WARNING
Valve full stroke count has
exceeded the warning limit.
VALVE REACTION TIME CLOSE
WARNING
Valve reaction time close trend has
exceeded the warning limit.
VALVE REACTION TIME OPEN
WARNING
Valve reaction time open trend has
exceeded the warning limit.
Display message
Description
CALIBRATION CANCELLED
Calibration process has been
cancelled.
CALIBRATION SUCCESSFUL
Calibration process has ended
successfully.
EXTERNAL RESET
Device has been booted, i.e.
power-up reset.
FACTORY DEFAULTS ACTIVATED
Device parameters were changed
to factory settings.
REDUCED PERFORMANCE
DEACTIVATED
Recovery for reduced performance
activation.