7 SG9H 70 en
45
16
TYPE CODING
SWITCHGUARD SG9000H
1.
2.
3.
4.
5.
6.
7.
8.
SG
9
2
15
H
E6
/
D33
1.
PRODUCT GROUP
SG
Neles SwitchGuard SG9000H, Intelligent On/Off Valve Controller.
2.
SERIES CODE
9
Series 9000 Intelligent on/off valve controller with universal
shaft and attachment face according to standard VDI/VDE 3845.
Relevant shaft adapter included in mounting kits. When SG9000
is separate delivery, shaft adapter kit needs to be ordered
separately (see type coding for accessories).
3.
ENCLOSURE
IP66 / NEMA 4X
Standard temperature range -40° to+85 °C / -40° to +185 °F.
M20 x 1.5 conduit entry.
2
Standard epoxy coated anodized aluminium enclosure.
3
Full 316 stainless steel enclosure, no glass window.
4.
SPOOL VALVE
CONNECTIONS
12
Restricted capacity.
Stroke volume of actuator
0.3 - 6.7 dm
3
.
S, C1, C2 = 1/4 NPT
15
Standard capacity.
Stroke volume of actuator
> 0.6 dm
3
.
S, C1, C2 = 1/4 NPT
35
High capacity.
Stroke volume of actuator
> 3.5 dm
3
.
Not applicable to 3. sign "3".
S, C1, C2 = 1/2 NPT
37
Extended capacity.
For single acting actuators.
Stroke volume of actuator
> 6.5 dm
3
.
Not applicable to 3. sign "3".
S = 1/2 NPT, C2 = 1 NPT
5.
COMMUNICATION / INPUT SIGNAL RANGE
H
4–20 mA, HART communication.
6.
APPROVALS FOR HAZARDOUS AREAS
N
No approvals for hazardous areas.
X
ATEX and IECEx certifications:
II 1 G Ex ia IIC T6...T4 GaII 1 D Ex ia IIIC T90 °C...T120 °C Da
II 1 D Ex ta IIIC T90 °C...T120 °C Da
II 2 G Ex ib IIC T6...T4 GbII 2 D Ex ib IIIC T90 °C...T120 °C DbII 2 D
Ex tb IIIC T90 °C...T120 °C Db
Temperature range: T4: -40 to +80 °C; T5: < +65 °C; T6: < +50 °C.
II 3 G Ex nA IIC T6...T4 Gc
II 3 D Ex ic IIIC T90 °C...T120 °C Dc
II 3 D Ex tc IIIC T90 °C...T120 °C Dc
II 3 G Ex ic IIC T6...T4 GcII 3 D Ex ic IIIC T90 °C...T120 °C DcII 3 D
Ex tc IIIC T90 °C...T120 °C Dc
Temperature range: T4: -40 to +85 °C; T5: < +75 °C; T6: < +60 °C.
Available without limit switches or with ATEX or IECEx certified
inductive limit switches.
Z
INMETRO certifications:
Ex ia IIC T6...T4 Ga
Ex ia IIC T6...T4 Gb
Temperature range: T4: -40 to +80 °C; T5: < +65 °C; T6: < +50 °C.
Ex nA IIC T6...T4 Gc
Ex ic IIC T6...T4 Gc
Temperature range: T4: -40 to +80 °C; T5: < +65 °C; T6: < +50 °C.
Available without limit switches or with certified inductive limit
switches.
U
(U1)
(U2)
cCSAus certifications
IS Class I, Division 1, Groups A, B, C, D, T6...T4
IS Class I, Zone 0, AEx ia, IIC T6...T4
Temperature range: T4; -40 to +80 °C, T5; < +65 °C, T6; < +50 °C.
NI Class I, Division 2, Groups A, B, C, D,T6...T4
NI Class I, Zone 2, Ex nA IIC, T6...T4
Temperature range: T4; -40 to +85 °C, T5; < +70 °C, T6; < +55 °C.
Not applicable with 7. sign "J". Not available with limit switches.
6.
APPROVALS FOR HAZARDOUS AREAS
E2
Flameproof enclosure, 1/2 NPT conduit entry.
cCSAus certifications:
Class I, Div 1, Groups B, C, D; Class II, Div 1, Groups E,F,G; Class III;
T6…T4, Enclosure type 4X
Ex d IIC T6…T4
AEx d IIC T6…T4
Ex tb IIIC T100 °C IP66
AEx tb IIIC T100 °C IP66
Temperature range: T6: -40 °C to +60 °C; T5: < +75 °C; T4: < +85 °C.
Available with or without limit switches.
E5
INMETRO certifications:
Ex d IIC T6...T4 Gb
Ex tb IIIC T80 °C...T105 °C Db
Available with or without limit switches.
E6
ATEX and IECEx certifications:
II 2 GD
Ex d IIC T6...T4 Gb
Ex tb IIIC T80 °C...T105 °C Db IP66
Temperature range: Ta according to Table 6.
Available with or without limit switches.
E7
ATEX and IECEx certifications with Russian machine plate:
II 2 GD
Ex d IIC T6...T4 Gb
Ex tb IIIC T80 °C...T105 °C Db IP66
Temperature range: See Table 6.
Available with or without limit switches
7.
OPTIONS OF VALVE CONTROLLER
T
Internal 2-wire (passive) position transmitter.
Analog position feedback signal, output 4–20 mA, supply voltage
12–30 V DC, external load resistance 0–780 Ω.
J
External junction box, 2 pcs M20x1.5 conduit entry.
NOT applicable to 6. sign "E2"
Junction box for all 4-20 mA wirings, including position
transmitter, if applicable. Junction box is attached to the
standard enclosure.
Not available with 6. sign "U".
Y
Special construction.
8.
LIMIT SWITCH TYPE
IP 66 / NEMA 4X enclosure.
Extension housing with additional conduit entries, max 4 pcs.
M20 x 1.5.
Inductive proximity switches
D33
Metso; SST Sensor Dual Module, NO, 8–125 V DC / 24–125 V AC
Temperature range: -40° to +82 °C / -40° to +179 °F.
Not applicable to 6. sign "X", "Z", or "U".
Usable up to SIL3 acc. to IEC61508.
D44
Metso; Namur Sensor Dual Module, 6 - 29 VDC, > 3 mA; < 1 mA,
NAMUR NC.
Temperature range -40° to +82 °C / -40° to +179 °F.
Not applicable to 6. sign "U".
Usable up to SIL3 acc. to IEC61508.
I02
P+F; NJ2-12GK-SN, 2-wire type, DC; > 3 mA; < 1 mA, NAMUR NC.
Intrinsically safe according to ATEX II 1 G Ex ia IIC T6.
Temperature range -40° to +85 °C / -40° to +185 °F.
Usable up to SIL3 acc. to IEC61508.
NOTE: In safety-related applications the sensor must be
operated with a qualified fail safe interface, such as
P+F KFD2-SH-EX1.
Not applicable to 6. sign "U".
I09
P+F; NCB2-12GM35-N0, 2-wire type, DC; > 3 mA; < 1 mA,
NAMUR NC.
Intrinsically safe according to ATEX II 2 G Ex ia IIC T6.
Temperature range -25° to +85 °C / -13° to +185 °F.
Usable up to SIL2 acc. to IEC61508.
Not applicable to 6. sign "U".
I32
Omron; E2E-X2Y1; 2-wire type; AC; <100mA; 24-240VAC.
Temperature range: -40° to +85 °C / -40° to +185 °F
Not applicable to 6. sign "X", "Z", or "U".