10 Service
Service actions
IMPORTANT
Servicing should only be carried out by persons with the
necessary expertise.
When replacing components in the SHK 200S / SHK
200S-6, only original spare parts should be used.
IMPORTANT
Switch (SF1) must not be put into mode „ ” before the
installation is filled with water. The compressor in the
heat pump can be damaged.
Emergency mode
Emergency mode is used in event of operational in-
terference and in conjunction with service. Hot water
is not produced in emergency mode.
Emergency mode is activated by setting switch (SF1)
in mode „ ”. This means that:
• The status lamp illuminates yellow
• The display is not lit and the control computer is
not connected.
• Hot water is not produced.
• The compressors are switched off. Charge pump
(EB101-GP12) and charge pump (EB102-GP12)
(if installed) are running.
• Accessories are switched off
• The heating medium pump is active.
• The emergency mode relay (K1) is active.
External additional heat is active if it is connected to
the emergency mode relay (K1, terminal block X1).
Ensure that the heating medium circulates through
the external additional heat.
Temperature
(ºC)
Resistance
(kOm)
Voltage
(VDC)
-40
351,0
3,256
-35
251,6
3,240
-30
182,5
3,218
-25
133,8
3,189
-20
99,22
3,150
-15
74,32
3,105
-10
56,20
3,047
-5
42,89
2,976
0
33,02
2,889
5
25,61
2,789
10
20,02
2,673
15
15,77
2,541
20
12,51
2,399
25
10,00
2,245
30
8,045
2,083
35
6,514
1,916
40
5,306
1,752
45
4,348
1,587
50
3,583
1,426
55
2,968
1,278
60
2,467
1,136
65
2,068
1,007
70
1,739
0,891
75
1,469
0,758
80
1,246
0,691
85
1,061
0,607
90
0,908
0,533
95
0,779
0,469
100
0,672
0,414
Chapter 10 |
Service
Summary of Contents for SHK 200S
Page 2: ......
Page 70: ...70 SHK 200S SHK 200S 6 Diagram of electrical connections Chapter 13 Technical data...
Page 71: ...71 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 72: ...72 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 73: ...73 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 74: ...74 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 75: ...75 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 76: ...76 SHK 200S SHK 200S 6...
Page 77: ...77 SHK 200S SHK 200S 6...
Page 78: ...78 SHK 200S SHK 200S 6...
Page 79: ......
Page 80: ...METRO THERM A S RUNDINSVEJ 55 DK3200 HELSINGE INFO METROTHERM DK WWW METROTHERM DK 08 242 1909...