54
SHK 200S
SHK 200S-6
Menu 5.5 - factory setting service
All settings can be reset (including settings available
to the user) to default values here.
IMPORTANT
When resetting, the start guide is displayed the next time
the control module is restarted with factory settings.
Chapter 9 |
Control
IMPORTANT
The signal for the AUX inputs must be a zero-voltage sig-
nal (make-break contact).
IMPORTANT
Menu 5.3.20 is inactive in the factory settings. For this menu
function to be active, installation of the EMK accessory is
required and its activation in the accessories menu 5.2.4.
A detailed description of programming the accesso-
ries can be found in the instructions for the individual
accessories.
Menu 5.3.20 - flow sensor
Menu 5.4 - soft in/outputs
In this menu, you can select which input on the input
card (AA3) can be connected to an external signal
(page 73).
Available entries on terminal strips AUX1-3 (AA3-X6:
9-14). The AUX inputs are freely programmable and
allow the introduction of additional functions using ex-
ternal signals.
Input AA3-X7 is used for the built-in QN12 (heating /
cooling) valve.
Factory setting:
IMPORTANT
Menu 5.3.16 is inactive in the factory settings. For this
menu function to be active, you must install the HTS 40
accessory and activate it in the accessories menu. 5.2.4.
A detailed description of programming the accesso-
ries can be found in the instructions for the individual
accessories.
Menu 5.3.16 - humidity sensor
Menu 5.6 - forced control
Menu 5.7 - start guide
Menu 5.8 - quick start
You can force control the different components in the
control module and any connected accessories here.
This menu is used to test individual components of
the SHK 200S / SHK 200S-6.
The first time you start the SHK 200S / SHK 200S-6,
the start guide starts automatically. In this menu we
have the ability to run it manually. For more informa-
tion about the start guide, see page 38.
It is possible to start the compressor from here.
Menu 5.9 - floor drying function
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70°C
Default value:
temp. period 1 20 °C
temp. period 2 30 °C
temp. period 3 40 °C
temp. period 4 45°C
temp. period 5 40 °C
temp. period 6 30 °C
temp. period 7 20 °C
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven pe
-
riods are to be used, set the remaining period times
to 0 days.
Mark the active window to activate the underfloor dry
-
ing function. A counter at the bottom shows the num-
ber of days the function has been active.
CAUTION
There must be a heating or hot water demand to start
the compressor
CAUTION
Do not quick start the compressor too many times over
a short period of time as this may damage the com-
pressor and its surrounding equipment.
ADVICE
If operating mode "add. heat only" is to be
used, select it in menu 4.2.
Summary of Contents for SHK 200S
Page 2: ......
Page 70: ...70 SHK 200S SHK 200S 6 Diagram of electrical connections Chapter 13 Technical data...
Page 71: ...71 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 72: ...72 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 73: ...73 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 74: ...74 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 75: ...75 SHK 200S SHK 200S 6 Chapter 13 Technical data...
Page 76: ...76 SHK 200S SHK 200S 6...
Page 77: ...77 SHK 200S SHK 200S 6...
Page 78: ...78 SHK 200S SHK 200S 6...
Page 79: ......
Page 80: ...METRO THERM A S RUNDINSVEJ 55 DK3200 HELSINGE INFO METROTHERM DK WWW METROTHERM DK 08 242 1909...