27
Connecting emission sensor: 1 – exhaust temp.
sensor type CT2S, 2 – sensor lead, 3 – flue.
Caution: Opening the boiler door
can
cause
the
emission
temperature to
exceed the
sensor‘s
thermal
resistance,
which can burn the sensor out.
12.9
Checking temperature sensors
Temperature sensors CT4/CT6-P/CT2S can be
checked by measuring their resistance at the
given temperature. In the case of finding
significant differences between the value of
measured
resistance
and
the
values
presented in the table below, the sensor must
be changed.
CT4 (KTY81)
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
CT6-P (PT1000) – weather
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
-25
901,6
901,9
1000,2
-20
921,3
921,6
921,9
-10
960,6
960,9
961,2
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2
CT2S (PT1000) - exhaust
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
999,7
1000,0
1000,3
25
1096,9 1097,3
1097,7
50
1193,4 1194,0
1194,6
100
1384,2 1385,0
1385,8
125
1478,5 1479,4
1480,3
150
1572,0 1573,1
1574,2
12.10
Connection of boiler room
thermostat
Note: the boiler room thermostat
should be switched off if the whole
central heating system of the
building is supplied through a mixing
valve equipped with electric servo.
The regulator may work with mechanical or
electronic room thermostat, which opens the
contacts once the preset temperature has
been achieved.
Set-up the operation of room thermostat in:
Boiler settings
Room thermostat
Thermostat selection
Universal
Once the preset room temperature
has been reached, thermostat opens
its contacts and the display shows:
.
Once the temperature in the room, in which
the room thermostat is installed, has reached
the preset value, regulator reduces the preset
boiler temperature by the value set in Inc. p.
b. temp. thermostat and the display shows
. This will cause longer breaks in boiler
operation (the boiler will remain in
SUPERVISION mode) and the same,
temperature in heated rooms will drop.
Moreover, the boiler pump (CH pump) may be
interlocked for a certain time by opening the