42 

 

15.5

 

Feeder temp. sensor damaged 

This  alarm  occurs  in  case  of  damage  of  fuel 
feeder  temperature  sensor  and  excess  of  its 
measurement  range.  To  reset  the  alarm  -
switch OFF and  ON the regulator.  Check the 
sensor and replace, if necessary.  

 

Checking  temperature  sensors 
described  in  this  manual,  in 
point.12.9. 

15.6

 

Exhaust sensor temp. damaged 

This  alarm  occurs  in  case  of  damage  of 
exhaust temperature sensor and excess of its 
measurement  range.  To  reset  the  alarm  -
switch OFF and ON the regulator. Check the 
sensor and replace, if necessary.  

 

Checking  temperature  sensors 
described  in  this  manual,  in 
point.12.9. 

15.7

 

Unsuccessful firing up attempt 

This alarm occurs after the third unsuccessful 
automatic  furnace  firing  up  attempt.  The 
reason  behind  this  alarm  occurrence  can  be 
among other things: malfunctioning igniter or 
ventilator, malfunction of fuel feeder system, 
incorrect  parameter  setting,  insufficient  fuel 
quality or lack of fuel in the container. 
The  alarm  can  be  reset  by  pressing  the 
encoder “TOUCH and PLAY” knob or restarting 
the power supply. 

 

Attention! 

Before 

work 

continuation  it  is  required  to 
check,  if  in  the  combustion 
chamber  there  was  a  large 
accumulation of unburned fuel. If 
it is the case, than it is required to 
remove this excessive fuel. Firing 
the  boiler  with  an  fuel  overdose 
can  lead  to  an  explosion  of 
combustible gases!.  

15.8

 

Exhaust temperature not met. 
Check fuel quality 

This alarm is sounded when the exhaust gases 
are not heated above the lack of fuel detection 
threshold in the exhaust temperature increase 
time.  The  alarm  prevents  filling  the 
combustion chamber with unburnt fuel. Check 
the quality and moisture of the fuel. 
The  alarm  can  be  reset  by  pressing  the 
encoder “TOUCH and PLAY” knob or restarting 
the power supply. 

15.9

 

Boiler overheating STB, open 
contact 

 

   

This  alarm  occurs  after  activation  of 
independent  safety  thermostat  that  secures 
the boiler against overheating. The burner will 
then  be  deactivated.  After  the  boiler 
temperature  will  drop  down  it  is  required  to 
unscrew  an  oval  STB  lid  and  then  press  the 
Reset button.  

15.10

 

Max exhaust temperature 
exceeded. Sensor damage danger! 

This alarm occurs only when using the GRATE 
and  exceeding  the  maximum  exhaust 
temperature.  The fan is turned off. Its aim is 
to  protect  the  exhaust  temperature  sensor 
from  being  damaged  by  temperatures 
exceeding  its  resistance  level.  When  the 
temperature on the boiler drops, the regulator 
returns to normal operation. 
The  alarm  can  be  reset  by  pressing  the 
encoder “TOUCH and PLAY” knob or restarting 
the power supply. 

15.11

 

No communication 

The control panel is being linked with the rest 
of  the  electronics  with  RS485  digital 
communication link. In case a cable of this link 
will  be  damaged,  an  alarm  will  occur  on  the 
screen  with  the  information  “CAUTION!!!  No 
communication”. 
The  controller  doesn’t  stop  to  operate  and 
works 

normally 

with 

before 

preset 

parameters.  It  is  required  to  check  the 
connection  cable  between  control  panel  and 
the module and replaced it with a new one or 
repair it. 

15.12

 

Unsuccessful attempt of buffer 
loading 

This  feature  has  an  application  only  after 
module  B  connection.  It  is  a  silent  alarm, 
which informs about unsuccessful attempt of 
adding  fuel  from  additional  fuel  container 
(bunker)  to  boiler  container.  In  case,  when 
during  preset  time  of  container  loading,  a 
sensor  in  this  container  will  not  detect  the 
increase  of  fuel  level,  this  alarm  will  occur. 
This  signalisation  does  not  shut  down  boiler 
automatic operation. 

15.13

 

No power supply 

This alarm occurs after power to the regulator, 
in  the  case  of  early  no  power  supply.  The 

Summary of Contents for ecoMAX 860P

Page 1: ...room panel ecoSTER200 and internet module ecoNET300 are not part of standard equipment regulator USER MANUAL AND INSTALLATION ISSUE 1 1 APPLIES TO SOFTWARE MODULE PANEL v 01 XX XX v 01 XX XX 02 2017 e...

Page 2: ...ed to water PRINCIPLES INDIVIDUAL FUZZY LOGIC The regulator must be programmed individually for the given type of boiler and fuel It is inadmissible to change the type of gear motor fan and to make ot...

Page 3: ...WEATHER SENSORS CONNECTION 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF BOILER ROOM THERMOSTAT 27 12 11 CONNECTION OF MIXER S ROOM THERMOSTAT 28 12 12...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...al is a supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both part...

Page 6: ......

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P...

Page 8: ...dule Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decre...

Page 9: ...increase from mixer circulation increasing preset temperature for loading buffer warning HUW disinfection mode is active 4 way valve partially closed active return protection 5 fan operation symbol 6...

Page 10: ...itionally adjusted with individual fuel feeding times and fan speeds affecting the actual output of the boiler The output level parameters are accessible through the menu Boiler Settings Output modula...

Page 11: ...HUW container parameter Off set HUW priority using the Priority parameter in this case the CH pump is deactivated to speed up filling of the HUW container set simultaneous operation of the CH and HUW...

Page 12: ...a room thermostat which will equalize the inaccuracy of selecting heating curve if the selected heating curve value is too high In such case it is necessary to set the value of preset mixer temperatu...

Page 13: ...e selected heating curve value is too high if the outdoor temperature drops and the room temperature drops as well the selected heating curve value is too low if during frosty weather the room tempera...

Page 14: ...el is burned off In order to change modes turn the regulator off and on by clicking Work mode in the Current information tab 8 19 Manual control Regulator offers possibility to manual start of working...

Page 15: ...f done properly will set the parameters Feeder efficiency and Tank capacity which can be found in Service Settings Boiler settings 8 21 Information Information menu allows to preview temperatures bein...

Page 16: ...16...

Page 17: ...17 INSTALLATION AND SERVICE SETTINGS ecoMAX 860P...

Page 18: ...re set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unn...

Page 19: ...temperature 55 C menu Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max pres...

Page 20: ...ings Buffer settings Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service...

Page 21: ...he controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condensation or be exposed to effects of water 12 2 Mounting requirements Regu...

Page 22: ...e terminals and the leads Connection cables should not have contact with surfaces which temperature exceeds cables nominal operating temperature Terminals 1 22 are designed to connect devices supplied...

Page 23: ...the lead from the connector it is not allowed to coil excess of the cable and to leave not connected leads inside the casing of the regulator 1 cable outlets 2 holdfasts placing should be broken out...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...ensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Weather sensors connection The regulator cooperates solely with t...

Page 27: ...74 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 12 10 Conne...

Page 28: ...serve boiler gas or oil eliminating the necessity of enabling or disabling this boiler manually The reserve boiler will be enabled if the temperature of the pellet boiler drops and disabled when the p...

Page 29: ...iler circuit pipes Use pipes of large cross section for gravitational boiler circuit Electric diagram for switching valve of the reserve boiler where 1 regulator 2 reserve boiler 3 4 relay RM 84 2012...

Page 30: ...umentation of valve manufacturer and check whether the valve is properly connected calibrate factor of mixer valve opening To do this disconnect power supply of the regulator and set the selector on h...

Page 31: ...two wire connection power supply of 12V DC and rated current of min 200mA is required Disconnect GND and 12V wires from the module 2 and re connect them to external power supply unit arranged near eco...

Page 32: ...there should be written new software in the pfc format as a 2 files a file with the panel software and a file with the module A software Software files should be placed directly on the memory card do...

Page 33: ...nly water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max boiler temperature B...

Page 34: ...parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm feed time Hall sensor control Min RP...

Page 35: ...ERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The p...

Page 36: ...These times may be edited in a special menu accessible only to the manufacturer of the boiler 14 2 BOILER Boiler settings Grate Max ignition time When this time is exceeded ant the exhaust temperatur...

Page 37: ...the status of the thermostat are sent from the room panel Pump Off by thermostat Available options No the CH boiler pump is not switched off when the room thermostat is activated YES the CH boiler pu...

Page 38: ...nsion time value Circulation pump standstill time It is the time between periods of circulation pump operation and it is defined by the parameter circulation standstill time recommended setting is bet...

Page 39: ...sing the set temperature above the value given for this parameter _ when the Mixer support On then the mixer pump will shut down by max mixer temperature 5 C which protects the floor against destructi...

Page 40: ...SETUP Show advanced setup Available options YES shows hidden parameters which edition is not recommended NO hides hidden parameters 14 7 RESTORE DEFAULT SETTINGS Restore default settings Restoring th...

Page 41: ...function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The function of protection against flame recession is inoperative if the regulator is not...

Page 42: ...the encoder TOUCH and PLAY knob or restarting the power supply 15 9 Boiler overheating STB open contact This alarm occurs after activation of independent safety thermostat that secures the boiler agai...

Page 43: ...d by scale deposit To do this these components are periodically every 167h switched on for few seconds In this way the pumps are protected from immobilization caused by scale deposits Therefore during...

Page 44: ...44...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Reviews: