Can I use my Fireplace during power outages?
During the power outage, the fireplace
’s
burner will function as well as the flame height adjustment. The fans will not
function.
What maintenance is required?
Required Annual Maintenance
The following procedures must be performed each year by a qualified installer, service agency or the gas supplier.
Note: Any adjustments to burner, pilot or logs must be done by a qualified installer, service agency or the gas supplier.
Recommended steps for yearly maintenance:
1.
Clean all lint and dust build-up around the control. Inspect the condition of any wiring under the burner for melting or
damage.
2.
Clean pilot light thermocouple, thermopile and sparker rod using emery cloth. Vacuum clean pilot light assembly.
3.
Visual check of pilot flames is required. Pilot flame must overlap
thermocouple tip and top 3/8” of thermopile
r and burner
ignition ports always. Especially for LP gas applications, always verify visible pilot flame length is at least 1" long.
4.
Vacuum all burner ports. Be sure the burner ports are "open".
5.
V
isual check of main burner’s
rear and front flames is required.
6.
Remove logs and coals and clean away any foreign matter (lint, carbon, etc.) on the burner and logs.
7.
Clean under side of the logs for any carbon deposits. Note: Logs should be visually checked for carbon buildup. If carbon
deposits are visible on logs, unit should be turned off and a qualified installer, service agency or the gas supplier
contacted. Be sure logs are re-installed per instructions.
8.
Check condition of glass door gasket, gasket must seal tightly over firebox. Inspect gasket along top and sides of glass. If
gasket bulb along top edge or side top areas are discolored to a white color appearance (through the whole thickness of
the gasket bulb
in a 3” to 12” long area) and the gasket adhesive in no longer functional to stick to glass, then replace the
gasket.
9.
Visually inspect the vent terminal (vent cap) for leaves, twigs and other debris accumulation. Clean if required.
10.
Clean door glass..
Summary of Contents for CHELSEA M-27
Page 2: ...85 03 01120 M27 Page 2 HOMEOWNER NOTES ...
Page 16: ...85 03 01120 M27 Page 16 Figure 3 8 Figure 3 7 ...
Page 35: ...85 03 01120 M27 Page 35 Approved Vent Systems ...
Page 62: ...85 03 01120 M27 Page 62 ...
Page 64: ...85 03 01120 M27 Page 64 ...
Page 65: ...85 03 01120 M27 Page 65 VERTICAL THROUGH THE ROOF VENTING USING THREE 900 ELBOWS ...
Page 69: ...85 03 01120 M27 Page 69 ...
Page 70: ...85 03 01120 M27 Page 70 ...
Page 71: ...85 03 01120 M27 Page 71 ...
Page 72: ...85 03 01120 M27 Page 72 ...
Page 73: ...85 03 01120 M27 Page 73 ...
Page 74: ...85 03 01120 M27 Page 74 ...
Page 103: ......