Rough Framing Dimensions
The Rough Framing Height must be maintained to allow this fireplace and the 90-degree elbow connected directly to the top,
on certain vent systems, to slide into the framing cavity. Once the fireplace is positioned inside the framed cavity, a secondary
nailer stud should be added at a minimum height of 38 inches above the floor level of this fireplace. The nailer stud will allow
for securing facing materials.
Special consideration for vertical
vent systems
If a straight-up vertical vent system is being
considered, the top plate on the front wall of the
chase will need to be notched to allow the proper
1” clearance from the top plate to the vertical
vent pipe. Furthermore, all framing headers and
members that are located within the 1” clearance
requirement to the vent stack or vent components must be positioned on edge (on the 1-
1/2” edge) to allow proper clearance
to the vent stack or component.
Figure 3-11 FRAMING METHOD
Figure 3-12 VERTICAL VENT SPECIAL REQUIREMENT
Minimum Rough Framing Dimensions
DESCRIPTION
DIMENSION (INCHES)
A
Width
29-1/2
B
Height
49
”
C
Depth
14
”
D
Unit Base to Room Ceiling
60”
E
Unit Base to 8” Mantel
47”
Summary of Contents for CHELSEA M-27
Page 2: ...85 03 01120 M27 Page 2 HOMEOWNER NOTES ...
Page 16: ...85 03 01120 M27 Page 16 Figure 3 8 Figure 3 7 ...
Page 35: ...85 03 01120 M27 Page 35 Approved Vent Systems ...
Page 62: ...85 03 01120 M27 Page 62 ...
Page 64: ...85 03 01120 M27 Page 64 ...
Page 65: ...85 03 01120 M27 Page 65 VERTICAL THROUGH THE ROOF VENTING USING THREE 900 ELBOWS ...
Page 69: ...85 03 01120 M27 Page 69 ...
Page 70: ...85 03 01120 M27 Page 70 ...
Page 71: ...85 03 01120 M27 Page 71 ...
Page 72: ...85 03 01120 M27 Page 72 ...
Page 73: ...85 03 01120 M27 Page 73 ...
Page 74: ...85 03 01120 M27 Page 74 ...
Page 103: ......