85-03-01120
M27
Page
17
M27 Fireplace Ratings Information
This Mendota Fireplace can be installed directly on top of a metal, masonry or wood structural surface.
ELECTRICAL REQUIREMENTS
: 120 Volts AC, 1.5 Amps (minimum line voltage allowed 110 Volts AC) REQUIRED
GAS SUPPLY PRESSURE
:
NAT. GAS: 7" W.C. [5.0" W.C. MIN., 11" W.C. MAX.]
L.P. GAS: 11" W.C. [11" W.C. MIN., 13" W.C. MAX.]
LP GAS CONVERSION KIT
: This Fireplace comes configured for use with Natural Gas. To convert the Fireplace for use with LP
Gas, install: LP GAS CONVERSION KIT #HA-48-00025.
GAS INPUT RATES
High Fire
Low Fire
BTUH. (MODEL M-27) NAT. GAS
27,000
6,750
BTUH. (MODEL M-27) LP GAS
25,000
7,000
ORIFICE SIZES
…………
[0-2000ft (610 m)]: REAR BURNER: #45 NG [#56 L.P.]
–
FRONT BURNER: #51 NG [#59 LP]
[2000-4500ft (610-1370 m)]: REAR BURNER: #46 NG [#57 L.P.]
–
FRONT BURNER: #52NG [#60 LP]
P.4 FIREPLACE EFFICIENCY
..........70.0%
FLUE VENTING
............COAXIAL RIGID- 4
” DIAMETER EXHAUST &
6-5/8
” DIAMETER
AIR INLET AND APPROVED VENT CAPS
All UL Listed Coaxial Rigid 4
”X
6-5/
8” Vent pipe components and vent caps are approved for use. Do not mix components of
different brands or series. Always use the same brand and series components throughout the entire vent system.
MINIMUM CLEARANCES TO COMBUSTIBLE CONSTRUCTION
UNIT TO FLOOR
0in. (0mm)
GLASS EDGE TO ADJACENT SIDEWALL 12 in. (305 mm)
UNIT TO ENCLOSURE SIDEWALL
0 in. (0 mm)
VENT PIPE TOP TO COMBUSTIBLES
3in. (51mm)
UNIT TO ENCLOSURE BACK WALL
1 in. (25 mm)
VENT PIPE SIDES TO COMBUSTIBLES
1in. (25mm)
UNIT TOP TO ENCLOSURE CEILING
1-1/2 in. (41 mm) VENT PIPE BOTTOM TO COMBUSTIBLES 1in. (25mm)
UNIT BOTTOM TO ROOM CEILING
60in. (152.4 cm)
DISTANCE TO
8” MANTLE ABOVE TOP CONVECTION AIR DISCHARGE OPENING
13 in. (330 mm)
MINIMUM COMBUSTIBLE ROUGH FRAMING DIMENSIONS
WIDTH = 29-1/2
” (74.9 cm)
HEIGHT = 49
” (124.6 cm)
DEPTH = 19-
1/2” (35.6 cm)
NET WEIGHT
................175 lbs. (Team Lift recommended)
BARRIER SCREEN
: A barrier screen that has been certified for use with this Fireplace must be installed on the Fireplace when it
is in use. The barrier screen will prevent accidental contact with the glass door face, which could result in a severe burn.
SAFETY
: AGA certified, electronic ignition IPI system activated with thermostatic remote control.
CERTIFIED TO
: ANSI Z21.88-2016
This Mendota Gas Fireplace has been tested and certified by:
Intertek Testing Services, 8431 Murphy Drive, Middleton, WI 53562\
ICBO#AA647-4
Summary of Contents for CHELSEA M-27
Page 2: ...85 03 01120 M27 Page 2 HOMEOWNER NOTES ...
Page 16: ...85 03 01120 M27 Page 16 Figure 3 8 Figure 3 7 ...
Page 35: ...85 03 01120 M27 Page 35 Approved Vent Systems ...
Page 62: ...85 03 01120 M27 Page 62 ...
Page 64: ...85 03 01120 M27 Page 64 ...
Page 65: ...85 03 01120 M27 Page 65 VERTICAL THROUGH THE ROOF VENTING USING THREE 900 ELBOWS ...
Page 69: ...85 03 01120 M27 Page 69 ...
Page 70: ...85 03 01120 M27 Page 70 ...
Page 71: ...85 03 01120 M27 Page 71 ...
Page 72: ...85 03 01120 M27 Page 72 ...
Page 73: ...85 03 01120 M27 Page 73 ...
Page 74: ...85 03 01120 M27 Page 74 ...
Page 103: ......