The table below shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Setting Logic 1-4
disabled
And
Or
Activates the logic function and
set the logical operation
Object type 1-4
Switch
Scene
Value
Forcible control 2 Bit
Sets the object type for sending
a value when the logic
operation is fulfilled
Scene number/ value/
forcible control
any value according to DPT
Setting only available with
Object type Scene / Value /
Forcible control 2 Bit
Sending condition (only
at object type Switch)
not automatic
at input telegram
at change output
at change output
(send only 0)
at change output
(send only 1)
At the object type "Switch" the
transmission condition can be
defined as well as a
transmission filter
Invert output (only at
object type Switch)
No
Yes
Determines whether the
output signal should be
inverted or not
Table 73: Settings - Logic 1-4
The corresponding communication object is displayed depending on the object type of the logic
operation:
Number
Name
Length
Usage
67
Logic
–
Output 1
1 Bit/
1Byte/
2 Bit
Output of the logic operation
Table 74: Communication object - Logic 1-4
If a logic operation is fulfilled, the corresponding value is transmitted.
For the object type "Switch", a send condition or a send filter for the output can be defined. The logic
operation may e.g. at each input telegram, send only when the output of the logic operation changes,
or only 1 or 0 are sent out. In addition, the output can be inverted with the object type "Switching",
thus making a 0 to a 1 and a 1 to a 0.