Technical Manual Glass Push Button II Smart BE-GT2xx.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 •
Fax: +49-2263-4588
• knx@mdt.de • www.mdt.de
59
4.3.2.4 Send value after state
;
Single-button function
The function "Send values - Send value after state" can send a fixed value according to the set
datapoint type and when the key is released a fixed value according to the set datapoint type.
The following figure shows the available settings:
Figure 27: Settings "Send value" - "Send value after state"
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
DPT 2.001
Switch control
DPT 5.001 Percent
DPT 5.005
Decimal factor
DPT 17.001
Scene number
DPT 9.001 Temperature
DPT 9.004 Brightness
DPT 232.600 RGB value
Sets the data point type to be
sent
Table 36: "Send value" - "Send value after state"
The value to be sent can be set according to the set datapoint type for pressing and releasing the key.
The following table shows the available communication objects:
Number
Name
Length
Usage
0
Push button 1
–
switch
control, percent value
…
Sending the switching value; DPT depending on
the parameter setting
3
Push button 1
–
State for
display
Receives the state; DPT dependent on
parameter settings
Table 37: Communication objects "Send value" - "Send value after state"