The table below shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
1 Byte (0...100%)
B te … 55
Sets the datapoint type for the
value shift
Lower limit
0-100%/0-255
[0/0]
Sets the lower limit value for
the value shift
Upper limit
0-100%/0-255
[100%/255]
Sets the upper limit value for
the value shift
Step width
0-100%/0-255
[10%/10]
Sets the step width between
two sending commands
Repeated sending at pressed
key
not active
active
Activation of the sending
repetition while pressing the
button
Repetition time
200ms-3s
[1s]
Repetition time between two
telegrams while pressing the
button
Switching considers status
object
x
Yes
x
No
Setting whether the value
should be moved according to
the current status
Table 33: "send values" - shift values
Principle of operation:
The function "shift value" moves the set datapoint type within the set limits. When the "Down"
button is pressed, the set step width is subtracted from the last value and sent. When the "Up"
button is pressed, the set step width is added to the last value and sent.
Lower/Upper limit:
Within these limits, the value is shifted. The function never falls below the lower limit value and does
not exceed the upper limit value.
Step width:
The step width indicates the difference between two transmitted telegrams. Example: step witdth is
set to 10%. If the value 10% was sent with the previous transmission, the value 20% is sent with the
next "up" command..
Repeated sending at pressed key:
Repeated transmission while holding down the key allows the function to increase/decrease the
value until the upper/lower limit is reached.
Switching considers status object:
If the status value is taken into account, the key function sends the next value depending on the last
received status value. If a status value of 15% and a step size of 10% were selected, then the value of
25% would be sent with the next "up" command. If the status value is not taken into account, the
push button memorizes the last value that was sent and sends the next value regardless of the status
value.