16-ALARMS
Technical Dept. - All rights reserved - Reproduction prohibited
NEGATIVE PRESSURE INSIDE THE HOPPER WITH FACTORY-SET PARAMETERS AND A DRAUGHT OF 5 Pa (MINIMUM
RECOMMENDED)
POWER
P1
P2
P3
P4
P5
VALUES
6 kW
13.7/14.2 Pa
15.1/15.6 Pa
17.1/17.5 Pa
19.1/19.5 Pa
22.0/22.2 Pa
Draught
95°C
110°C
125°C
141°C
165°C
Smoke temperature
8 kW
13.8/14.3 Pa
15.6/16.1 Pa
17.8/18.0 Pa
21.7/22.2 Pa
26.1/26.6 Pa
Draught
104°C
119°C
145°C
148°C
184°C
Smoke temperature
10 kW
15.9/16.3 Pa
20.4/20.9 Pa
25.8/26.3 Pa
31.8/32.3 Pa
36.5/37.0 Pa
Draught
108°C
°C
150°C
°C
230°C
Smoke temperature
12 kW
16.5/17.3 Pa
20.4/20.9 Pa
25.8/26.3 Pa
31.8/32.3 Pa
36.5/37.1 Pa
Draught
118°C
127°C
155°C
172°C
195°C
Smoke temperature
14 kW
17.6/18.0 Pa
19.8/20.4 Pa
23.1/23.7 Pa
28.9/29.6 Pa
37.8/38.2 Pa
Draught
118°C
131°C
161°C
187°C
210°C
Smoke temperature
PLEASE NOTE The indicated negative pressure readings may differ by ±1Pa based on flue gas temperature. Likewise, flue gas temperature
may differ by ±10°C based on fuel quality or appliance cleanliness.
Changing the smoke fan revolutions
In the event the installation presents problems in extracting smoke (lack of draft or even pressure in the duct), it is possible to increase the
smoke and ash extraction speed. This change resolves all potential problems related to pellets clogged in the brazier and deposits forming
at the bottom of the brazier itself caused by poor quality fuel or fuel that produces a lot of ash. The values available range from -30% to
+50%, with increments of 10 percent at a time. Negative variation may be required if the flame is too low.
To edit this parameter, proceed as follows:
• Press the “menu” key.
• Use the arrow keys to scroll through and select “Settings”
• Press “menu” to confirm.
• Scroll with the arrows and select “Fume rpm Var.”
• Press “menu” to confirm.
• Edit the % by using the + - keys.
• Press ‘’menu’’ to confirm and ‘’esc’’ to exit.