The arrow buttons are used to jog the guide in either
direction. This can be used to move the web in and out of the sensor during
the calibration process.
Use the sensor select button to select the sensor input channel
before calibration. Pressing this button alternates between the S1 and S2
sensor input channels.
Press
or
to exit and return to the previous screen.
Calibration Procedure:
..
Select which set of calibration values will be used.
Select S1 or S2 sensor input.
Press the START CALIBRATION button. The bar graph indicator will be
rescaled to show the full signal range of -32768 to +32767 on the selected
sensor input. The sensor signal level will also be displayed under the bar
graph as shown is the example screen below.
Move the web material completely out of the sensor field of view and press
the UNCOVER SENSOR button.
Move the web material into the sensor field of view until the entire
proportional band of the sensor is covered, and press the COVER SENSOR
button.
If the calibration was successful, the following message will appear.