www.maxcess.com
FIFE-500 MAX Narrow Web Guide
MI 2700XXXXX 18
CHAPTER 4
SENSOR SETUP
46 / 77
4.7 SENSOR SETUP
The factory sensor settings are for webs that are
100% opaque using the installed sensors. The sensor setup menu is used to
calibrate the FIFE-500 MAX Web Guiding System to maximize sensor signal
sensitivity when used with webs that are not totally opaque. This procedure
involves teaching the FIFE-500 MAX Web Guiding System using a sample of
the web material.
Navigation:
MANUAL
SETUP
SENSOR SETUP
The FIFE-500 MAX Web Guiding System stores separate calibration data for
the S1 and S2 sensor inputs so the procedure should be done on each
sensor input that will be used. The FIFE-500 MAX Web Guiding System can
store/recall up to four sets of calibration settings for S1 and S2 supporting
the possibility to store and quickly recall sensor settings for four different
web opacities.
Button Descriptions:
..
CALIBRATION SET These buttons select one of four sets
of calibration values. Only one calibration set may be active at any given
time with the active set indicated by the green LED on the button face. Set 1
is active by default. Touch the button for the desired set to make it active.
Note: This change takes effect immediately after saving
,
and in this case,
exiting this menu with the CANCEL button will not restore this calibration
to its previous setting.
Note: If calibration set 2, 3, or 4 is in use, the sensor button on
the Operator Level screen will reflect this by displaying a 2, 3, or
4 as shown here. When calibration set 1 is active, the sensor
button on the Operator Level screen will not display a number.