4.6 Testing the UPS
Before turning off the AC power to the intersection as a final test, verify proper
installation and ability to go ON BATTERY by placing the MANUAL BYPASS SWITCH
to BYPASS. The unit should immediately go ON BATTERY. When the MANUAL
BYPASS SWITCH is returned to UPS, the unit should go back On Line after AC Qualify
time. Then to test the UPS further, perform the self-test feature via the CONTROL
submenu (see Section 5.7 Control).
When performing the test below, if for any reason the unit fails to go ON BATTERY,
immediately restore the AC power for the intersection at the upstream circuit breaker.
Turn OFF the
upstream circuit
breaker.
The
OUTPUT Green LED
will
flash and the
LCD
displays
ON
BATT
, indicating that output
AC power is supplied from
battery power.
Observe the
Red Alarm LED
. If it is
on
or
flashes
, follow the troubleshooting sequence
as below:
1. Investigate the Alarm/Fault.
2. Perform a self-test with the load(s)
connected.
3. If it passes the self-test, verify that that
loads are operating normally.
4. See the troubleshooting table in the
manual.
5. Contact Customer Service.
Turn ON the upstream circuit
breaker.
Within 30 seconds the PTS
switches back to line power.
The Green Output LED is lit
and the display shows
"ON LINE".
TIP:
ATTENTION!
27
Summary of Contents for TRTC-2002-N1
Page 1: ......
Page 2: ...2...
Page 45: ...6 2 Menu Tree 45...
Page 46: ...46...
Page 47: ...47...
Page 48: ...48...
Page 76: ...HyperTerminal at a Glance 76...
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ...2017 Marathon Power Inc TRTC 2002 N1 User Manual_Jan_2017 2017 Marathon Power Inc...