4.2 Recommended Wiring
Consult a licensed electrician in accordance with local electrical codes.
1. AC Input Cords
a. UL Style 1015 CSA TEW 6 or 10 AWG
b. 105 stands of 30 AWG tinned copper
c. Rating 600V, 105°C, PVC Insulation
2. Power Interconnects between BBS components and 332A terminal blocks and busses.
a. UL Style 1015 CSA TEW 10 AWG
b. 105 stands of 30 AWG tinned copper
c. Rating 600V, 105°C, PVC Insulation
3. Relay connections
a. Insulated UL Style CSA TEW 18 AWG
b. 16 stands of 30 AWG tinned copper
c. Rating 600V, 105°C, PVC Insulation
4. DC Battery Connectors
a. Two-Part Modular Harness UL Style 1015 CSA TEW or Welding Style Cable or
equivalent, 6 AWG Stranded and 10 AWG Stranded
Verify the
UPSTREAM CIRCUIT BREAKER
is off.
Verify the
AC INOUT & OUTPUT CIRCUIT BREAKER
is off.
Verify the
BATTERY CIRCUIT BREAKER
is off.