111
High Pressure Cutout (HPCO) Control
Function
Stops the ice machine if subjected to excessive high-side
pressure.
The HPCO control is normally closed, and opens on a rise
in discharge pressure.
Specifications
Cut-out: 450 psig ±10
Cut-in: Automatic reset
(Must be below 300 psig to reset)
Check Procedure
1. Switch to OFF.
2. Connect manifold gauge.
3. Hook voltmeter in parallel across the HPCO, leaving
wires attached.
4. On water-cooled models, close the water service
valve to the water condenser inlet. On self-contained
air-cooled models, disconnect the fan motor.
5. Set to ON.
6. No water or air flowing through the condenser
will cause the HPCO control to open because of
excessive pressure. Watch the pressure gauge and
record the cut-out pressure.
n
Warning
If discharge pressure exceeds 460 psig and the HPCO
control does not cut out, press the power button to
stop ice machine operation.
Replace the HPCO control if it:
• Will not reset (below 300 psig)
• Does not open at the specified cut-out point
Summary of Contents for STH042 4/16
Page 2: ......
Page 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 145: ......