78
Analyzing Discharge Pressure
1. Determine the ice machine operating conditions:
Air temp. entering condenser
______
Air temp. around ice machine
______
Water temp. entering sump trough ______
2. Refer to “Cycle Times, 24 Hr. Ice Production and
Refrigerant Pressure Charts” on page 127 for ice
machine being checked.
Use the operating conditions determined in step 1 to find
the published normal discharge pressures.
Freeze Cycle
______
Harvest Cycle
______
3. Perform an actual discharge pressure check.
Freeze Cycle
PSIG
Harvest Cycle
PSIG
Beginning of
Cycle
__________
__________
Middle of
Cycle
__________
__________
End of
Cycle
__________
__________
4. Compare the actual discharge pressure (Step 3) with
the published discharge pressure (Step 2).
The discharge pressure is normal when the actual
pressure falls within the published pressure range for the
ice machine’s operating conditions. It is normal for the
discharge pressure to be higher at the beginning of the
freeze cycle (when load is greatest), then drop through
out the freeze cycle.
Summary of Contents for STH042 4/16
Page 2: ......
Page 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Page 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Page 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 145: ......